Electrical characteristics
EDUS281008
18
FTQ-PA + RZQ-P
7.3
Outdoor unit
RZQ18PVJU9 / RZQ24PVJU9
C: 3D064227C
(ground leakage circuit breaker).
SYMBOLS:
MCA : Minim
u
m Circ
u
it Amps (A)
MOP : Maxim
u
m O
v
erc
u
rrent Protecti
v
e De
v
ice (A) (See
N
ote 7)
MSC : Maxim
u
m c
u
rrent
w
hen starting the compressor. (A)
RLA : Rated Load Amps (A)
OFM : O
u
tdoor Fan Motor (A)
FLA : F
u
ll Load Amps (A)
K
W
: Fan Motor Rated O
u
tp
u
t. (k
W
)
N
OTES:
1. RLA is
b
ased on the follo
w
ing conditions:
Po
w
er s
u
pply : 60Hz 20
8
-230
V
Cooling:
Indoor temp:
8
0°FDB / 67°F
W
B
O
u
tdoor temp: 95°FDB
Heating
Indoor temp: 70°FDB
O
u
tdoor temp: 47°FDB / 43°F
W
B
2.
V
oltage range:
Units are s
u
ita
b
le for
u
se on electrical systems
w
here
v
oltage s
u
pplied to
u
nit terminal is not
b
elo
w
or a
b
o
v
e listed range limits.
3. Maxim
u
m allo
w
a
b
le
v
oltage
v
ariation
b
et
w
een
phases is 2
%
.
4. MCA represents maxim
u
m inp
u
t c
u
rrent.
MOP represents capacity
w
hich may accept MCA.
5. Select
w
ire size
b
ased on the
v
al
u
e of MCA.
6. MOP is
u
sed to select the circ
u
it
b
reaker.
The relationship between the starting time and the starting current:
Summary of Contents for FTQ-PA
Page 1: ...EDUS281008 Split System Air Conditioners Air Handling Unit FTQ PA RZQ P9 ...
Page 12: ...EDUS281008 Dimensions and service space FTQ PA RZQ P 9 1 3D06421 ...
Page 15: ...Piping diagrams EDUS281008 12 FTQ PA RZQ P 5 2 Outdoor unit RZQ18PVJU9 RZQ24PVJU9 3D062238B ...
Page 20: ...EDUS281008 Electrical characteristics FTQ PA RZQ P 17 1 7 2 Electric heater ...