![background image](http://html.mh-extra.com/html/daikin/ftq-pa/ftq-pa_engineering-data_2459379056.webp)
EDUS281008
Installation of outdoor unit
Installation of indoor / outdoor unit
53
2
C: 3PA60114-14Y
13
English
Perform the electric wiring work in accordance with the
•
“electric wiring diagram label”.
Make sure to turn OFF the branch switch and overcurrent
protective device before starting the work.
Perform grounding to the indoor units and outdoor units.
•
Use only copper wires.
•
Make sure to turn the power off before starting the electric
•
wiring work.
Do not turn ON any switch until the work is completed.
The outdoor unit has an inverter which generates noise and
•
charges the outer casing with the leakage current. The
outdoor unit should be grounded so that the effect of the
generated noise on other equipment can be reduced, and
that the outer casing can be discharged.
As this unit is equipped with an inverter, installing a phase
•
advancing capacitor will not only reduce the power factor
improvement factor, but may also cause the capacitor to
overheat due to high-frequency waves. Therefore, never
install a phase advancing capacitor.
Never push excessive electric wires into the units.
•
Protect electric wires with conduit tubes or vinyl tubes so
•
that they will not be damaged by edges of knock holes.
Fix electric wires with clamps as accessories so that they will
•
not come to contact with pipes and stop valves.
(Refer to “
7-3 Power supply wiring connection procedure
”.)
Connection example of whole system wiring
7-1
Power
Remote
controller
Indoor
unit
Ground
Power
Ground
Outdoor unit
16V
208/230V
208/230V
16V
'ROUND
leakage
circuit interrupter
Overcurrent
protective device
Branch switch
Routing power supply wiring and transmission
7-2
wiring
Let the power supply wiring with a conduit pass through one of
the knockout holes on the front or side cover, and let the
transmission wiring with a conduit pass through another
knockout hole.
For protection from uninsulated live parts, thread the power
•
supply wiring or the transmission wiring through the included
insulating tube and secure it with the included clamp.
I
ns
ul
a
t
ing
tu
be
(
a
cc
ess
o
r
y)
Cl
am
p
(
a
cc
ess
o
r
y)
Po
wer
s
upply
wiring
o
r
T
ransmissi
o
n
wiring
(
3in.
)
〈
Precautions when knocking out knock holes
〉
To punch the knockout hole, hit it with a hammer.
•
After removing the knockout, it is recommended that the
•
edges should be painted to prevent rusting.
CAUTION
Use conduit for both the power supply wiring and transmis-
•
sion wiring.
Outside the unit, make sure to keep the wirings 5 inches
•
away.
Otherwise, the outdoor unit may be affected by electrical
noise (external noise), and malfunction or fail.
Be sure to connect the power supply wiring to the terminal
•
block and secure it as described in “7-3 Power supply wiring
connection procedure”.
Fix the wiring between the units in accordance with
•
“7-4 Transmission wiring connection procedure”.
Secure the wirings with the clamps (accessory) so that do
•
not touch the piping.
Make sure the wirings will not be pinched by the front panel,
•
and close the panel fi rmly.
Route the conduit along the unit by using a elbow socket
•
and so on to prevent it from being stepped on.
Power supply wiring connection procedure
7-3
WARNING
Never connect power supply wiring to the terminal block for
•
remote controller wiring as this could damage the entire system.
Install an earth leakage circuit interrupter.
It is obliged to install an earth leakage circuit interrupter to
•
prevent electric shock and fi re accident.
Mod
el
Phase
and
frequency
Voltage
Max.Overcurrent
Protective
Device
Min.
Circuit
Amps.
R
ZQ
18PV
J
U
~
60
Hz
208/230V
20A
16.5A
R
ZQ
24PV
J
U
Summary of Contents for FTQ-PA
Page 1: ...EDUS281008 Split System Air Conditioners Air Handling Unit FTQ PA RZQ P9 ...
Page 12: ...EDUS281008 Dimensions and service space FTQ PA RZQ P 9 1 3D06421 ...
Page 15: ...Piping diagrams EDUS281008 12 FTQ PA RZQ P 5 2 Outdoor unit RZQ18PVJU9 RZQ24PVJU9 3D062238B ...
Page 20: ...EDUS281008 Electrical characteristics FTQ PA RZQ P 17 1 7 2 Electric heater ...