EDUS281008
Installation of outdoor unit
Installation of indoor / outdoor unit
45
2
3PA60114-14Y
5
English
40 or more
Branch switch
and overcurrent
protective device
Indoor remote
controller
60 or more
60 or more
40 or more
Branch switch
and overcurrent
protective device
60 or more
Indoor unit
(in.)
DANGER
Do not install unit in an area where fl ammable materials are
•
present due to risk of explosion resulting in serious injury or
death.
Refrigerant is heavier than air and replaces oxygen. A
•
massive leak could lead to oxygen depletion , especially in
basements, and an asphyxiation hazard could occur leading
to serious injury or death.
Installation place (unit: inch)
〈
Cautions on continuous installation
〉
The connection piping outlet direction in the continuous
•
installation shown in the fi gures below is frontward or down-
ward.
When routing the piping rearward, secure space of 10 in. or
•
more on the right side of the outdoor unit. (The unit of nu-
meric values below is “inch”.)
Make some space for wiring with conduit and servicing
•
between the units.
(A) When an obstruction is present on the air inlet side
When the upward area is open
•
When one outdoor unit is installed individually
(1)
When an obstruction is present only on the air inlet
•
side
4 o
r
m
o
re
When an obstruction is present on the both sides
•
4 o
r
m
o
re
4 o
r
m
o
re
4 o
r
m
o
re
When two or more outdoor units are installed side
(2)
by side
When an obstruction is present on the both sides
•
40 o
r
m
o
re
12 o
r
m
o
re
8 o
r
m
o
re
When an obstruction is present also in the upward area
•
When one outdoor unit is installed individually
(1)
When an obstruction is present also on the air inlet
•
side
20 o
r
l
ess
40 o
r
m
o
re
4 o
r
m
o
re
When an obstruction is present also on the air inlet
•
side and both sides
6 o
r
m
o
re
6 o
r
m
o
re
20 o
r
l
ess
6 o
r
m
o
re
40 o
r
m
o
re
When two or more outdoor units are installed side
(2)
by side
When an obstruction is present also on the air inlet
•
side and both sides
20 o
r
l
ess
8 o
r
m
o
re
40 o
r
m
o
re
12 o
r
m
o
re
40 o
r
m
o
re
Summary of Contents for FTQ-PA
Page 1: ...EDUS281008 Split System Air Conditioners Air Handling Unit FTQ PA RZQ P9 ...
Page 12: ...EDUS281008 Dimensions and service space FTQ PA RZQ P 9 1 3D06421 ...
Page 15: ...Piping diagrams EDUS281008 12 FTQ PA RZQ P 5 2 Outdoor unit RZQ18PVJU9 RZQ24PVJU9 3D062238B ...
Page 20: ...EDUS281008 Electrical characteristics FTQ PA RZQ P 17 1 7 2 Electric heater ...