SiENBE04-507A
Control Specification
Function and Control
75
3.15 Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –15°C by cutting jumper 8 (J8) on the PCB. If the
outdoor temperature falls to –20°C or lower, the operation will stop. If the outdoor temperature
rises, the operation will start again.
Caution
1. If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4. Cutting jumper 8 (J8) sets the indoor fan tap to the highest position. Notify the user about
this.
1
2
3
S80
PCB
J1
J3
J4
J5
J6
J7
J8
Cut J8 with nippers
or a similar tools.
S80
S90
S70
Summary of Contents for FTKS20D2VMWL
Page 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Page 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Page 215: ...Others SiENBE04 507A 206 Others...
Page 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Page 225: ...SiENBE04 507A iv Index...