![background image](http://html1.mh-extra.com/html/daikin/ftks20d2vmwl/ftks20d2vmwl_service-manual_2459361118.webp)
SiENBE04-507A
Service Check Function
Service Diagnosis
109
Check Method 2
1. Enter the diagnosis mode.
Press the 3 buttons (TEMP
s
,TEMP
t
, MODE) simultaneously.
The digit of the number of tens blinks.
H
Try again from the start when the digit does not blink.
2. Press the TEMP button.
Press TEMP
s
or TEMP
t
and change the digit until you hear the sound of “beep” or “pi pi”.
3. Diagnose by the sound.
H
“ pi ” : The number of tens does not accord with the error code.
H
“ pi pi ” : The number of tens accords with the error code.
H
“ beep ” : The both numbers of tens and units accord with the error code. (
→
See 7.)
4. Enter the diagnosis mode again.
Press the MODE button.
The digit of the number of units blinks.
(R4272)
(R4273)
(R4274)
(R4275)