SiENBE04-507A
Troubleshooting
Service Diagnosis
119
4.7
Unspecified Voltage (between Indoor and Outdoor Units)
Remote
Controller
Display
UA
Method of
Malfunction
Detection
The supply power is detected for its requirements (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong indoor unit PCB mounted
Indoor unit PCB defective
Wrong outdoor unit PCB mounted or defective
Troubleshooting
Check the indoor and outdoor unit
model numbers.
Match the compatible
models.
Change for the specified
PC board (1) or (2).
Replace the indoor unit PC
board (1) (or the outdoor
unit PC board).
(Q0347)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Indoor unit and outdoor
unit matched?
Matched compatibly?
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PC boards
with the Parts List.
Caution
NO
YES
NO
YES
Summary of Contents for FTKS20D2VMWL
Page 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Page 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Page 215: ...Others SiENBE04 507A 206 Others...
Page 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Page 225: ...SiENBE04 507A iv Index...