Troubleshooting
SiENBE04-507A
122
Service Diagnosis
4.10 Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
Decision
Conditions
The system judges the compressor lock, and stops due to over current.
The system judges the compressor lock, and cannot operation with position detection within
15 seconds after start up.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 10 minutes (normal)
Supposed
Causes
Compressor locked
Compressor harness disconnected
Troubleshooting
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Turn off the power. Disconnect the
harnesses U, V and W.
∗
Inverter checker
Part
No.:
1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R2842)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
System shut
down after errors repeated
several times?
Normal?
Emergency stop
without compressor
running?
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Caution
YES
NO
YES
NO
YES
NO
Summary of Contents for FTKS20D2VMWL
Page 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Page 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Page 215: ...Others SiENBE04 507A 206 Others...
Page 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Page 225: ...SiENBE04 507A iv Index...