SiENBE04-507A
Control Specification
Function and Control
67
3.6
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start.
Control in Each Zone
3.7
Heating Peak-cut Control
Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec. from
operation start.
Control in Each Zone
The heat exchange intermediate temperature of indoor unit controls the following.
(R4561)
Return from stop
Reset zone
Heat exchanger
thermistor temperature
Up zone
Keep zone
Drooping zone
Stop zone
0°C
3°C
5°C
7°C
13°C
Stop zone 65°C
Drooping zone
Keep zone
Up zone
Reset zone 46°C
56°C
53°C
51°C
Heat exchanger
thermistor
temperature
Summary of Contents for FTKS20D2VMWL
Page 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Page 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Page 215: ...Others SiENBE04 507A 206 Others...
Page 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Page 225: ...SiENBE04 507A iv Index...