3. OPERATION RANGE
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING [°C]*
* To avoid condensation and water dripping out the indoor unit.
DB: Dry bulb temperature
WB: Wet bulb temperature
The setting temperature range of the remote controller is 16°C
to 32°C depends on heating/cooling mode.
OUTDOOR UNIT
INDOOR
OUTDOOR
TEMPERA-
TURE
TEMPERA-
TURE
HUMID-
ITY
RN50
RN60
DB 18 to 32
80%*or
below
DB
– 10 to
46
RKS35/50/60
RXS35/50/60
DB 18 to 32
80%*or
below
DB
– 10 to
46
4MKS58/75
3MXS52/68
4MXS68/80
5MXS90
DB 18 to 32
80%*or
below
DB
– 10 to
46
5MKS90
DB 18 to 32
80%*or
below
DB
10 to 46
RZQ140/200/
250
DB 20 to 37 80%*or
below
DB – 5 to 46
WB 14 to 28
RZQG 71/100/
125/140
DB 18 to 37 80%*or
below
DB
– 15 to
50
WB 12 to 28
RZQSG 71/100/
125 /140
DB 20 to 37 80%*or
below
DB
– 15 to
46
WB 14 to 28
OUTDOOR UNIT
INDOOR
OUTDOOR
TEMPERA-
TURE
TEMPERA-
TURE
HUMID-
ITY
RXM35/50/60
DB 18 to 32
80%*or
below
DB
– 10 to
46
3MXM40/52/68
4MXM68/80
5MXM90
DB 18 to 32
80%*or
below
DB
– 10 to
46
RZAG71/100/
125/140
DB 18 to 37 80%*or
below
DB
– 20 to
52
WB 12 to 28
RZASG71/100/
125/140
DB 20 to 37 80%*or
below
DB
– 15 to
46
WB 14 to 28
HEATING [°C]*
* To avoid condensation and water dripping out the indoor unit.
DB: Dry bulb temperature
WB: Wet bulb temperature
The setting temperature range of the remote controller is 16°C
to 32°C depends on heating/cooling mode.
4. INSTALLATION SITE
Regarding places for installation
•
Is the air conditioner installed at a well-ventilated
place where there are no obstacles around?
•
Do not use the air conditioner in the following
places.
a. Filled with much mineral oil such as cutting oil
b. Where there is much salt such as a beach area
c. Where sulfured gas exists such as a hot-spring
resort
d. Where there are considerable voltage fluctua-
tions such as a factory or plant
e. Vehicles and vessels
f. Where there is much spray of oil and vapor
such as a cookery, etc.
g. Where there are machines generating electro-
magnetic waves
h. Filled with acid and/or alkaline steam or vapor
OUTDOOR UNIT
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
RXS35/50/60
DB
10 to 30
DB
– 15 to 24
WB
– 16 to 18
3MXS52/68
4MXS68/80
5MXS90
DB
10 to 30
DB
– 15 to 24
WB
– 16 to 18
RZQG71/100/
125/140
DB
10 to 27
DB
–19.5 to 21
WB
–20 to 15.5
RZQ200/250
DB
10 to 27
DB
– 14 to 21
WB
– 15 to 15
RZQSG71
DB
10 to 27
DB
– 14 to 21
WB
–15 to 15.5
RZQSG100/125/
140
DB
10 to 27
DB
– 14 to 21
WB
–15 to 15.5
RZQ140
DB
10 to 27
DB
– 19.5 to 21
WB
– 20 to 15.5
OUTDOOR UNIT
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
RXM35/50/60
DB
10 to 30
DB
– 15 to 24
WB
– 16 to 18
3MXM40/52/68
4MXM68/80
5MXM90
DB
10 to 30
DB
– 15 to 24
WB
– 16 to 18
RZAG71/100/125/
140
DB
10 to 27
DB
– 19.5 to 21
WB
– 20 to 15.5
RZASG71/100/125/
140
DB
10 to 27
DB
– 14 to 21
WB
– 15 to 15.5
4PEN465376-1.book Page 5 Wednesday, March 15, 2017 3:03 PM