EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22686-1

Installation manual

6

W

ATER

 

PIPING

 

INSULATION

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.

Protect the water piping against water freezing during winter period
(e.g. by using a glycol solution or heater tape).

R

EFRIGERANT

 

PIPING

 

INSULATION

To  prevent burning injuries by accidental touching the hot (max
135°C) discharge pipe, it must be insulated thoroughly. 

A minimum of insulation to protect the liquid pipe from damage is
advisable.

D

ISCHARGE

 

FROM

 

PRESSURE

 

RELIEF

 

DEVICES

Discharge of the refrigerant into installation area has to be in
accordance with local regulations. If required it is possible to connect
a 1" pipe to each pressure relief valve on the condenser. 

Cross section and lenght of the discharge line must comply with local
codes.

F

IELD

 

WIRING

Parts table

F1,2,3U.................. Main fuses for the unit

H1,4P..................... Indication lamp general operation

H2,5P..................... Indication lamp alarm

H3,6P..................... Indication lamp operation compressor

L1,2,3..................... Main supply terminals

PE.......................... Main earth terminal

S6S........................ Changeable input 1

S8L ........................ Flowswitch

S9L ........................ Contact that closes if the pump is working

S10S...................... Changeable input 2

S11S...................... Changeable input 3

S12S...................... Changeable input 4

S13S...................... Main isolator switch

- - - ......................... Field wiring

Power circuit and cable requirements

1

The electrical power supply to the unit should be arranged so
that it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit.

For a system with chillers in a DICN configuration, be sure to
provide a separate power circuit for every chiller.

Connection of the watercooled water chiller power 
supply

1

Using the appropriate cable, connect the power circuit to the L1,
L2 and L3 terminals of the unit.

In case the option "main isolator switch" is installed on the unit,
the power circuit must be connected to the terminals 2,4 and 6
of the main isolator switch.

2

Connect the earth conductor (yellow/green) to the earthing
terminal PE.

Interconnection cables

Voltage free contacts
The controller is provided with some voltage free contacts to
indicate the status of the unit. These voltage free contacts can
be wired as described on the wiring diagram. The maximum
allowable current is 4 A.

Remote inputs
Besides the voltage free contacts, there are also possibilities to
install remote inputs.
They can be installed as shown on the wiring diagram.
For units in DICN configuration, note the following:

Switch for remote on/off:

Units with status 

  or 

  will be controlled by the

remote on/off switch connected to the chiller defined as 

.

Units with status 

   

are controlled by the

switch connected to them.

See also operation manual: "Selecting local or remote on/off
control".

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

NOTE

Verify on the wiring diagram all electrical actions
mentioned below, in order to understand the operation
of the unit more deeply.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

A pump interlock contact must be installed in series
with the contact of the flowswitch(es)
 to prevent the
unit from operating without water flow. A terminal is
provided in the switch box for the electrical connection
of the interlock contact.
For units in a DICN configuration, every chiller can
either have an individual circulation pump or 1 pump
can discharge water in a distributor that leads water to
several chillers.
In both cases, all units must be equipped with an
interlock contact!

NOTE

Normally the unit will not operate if there is no flow
thanks to the standard installed flowswitch.
But as to have a double safety, you must  install
the pump interlock contact in series with the
contact of the flowswitch.
Operating the unit without flow will result in very
severe damage to the unit (freezing of the
evaporator)

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...

Page 14: ...3 shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this...

Page 15: ...er circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerg...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22686 1...

Reviews: