Installation manual

7

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22686-1

Remote dual setpoint switch:

The remote dual setpoint switch should only be connected to the
chiller defined as 

.

However in case the master drops out because of e.g. a power
supply failure, it might be interesting to have the dual temperature
switch installed to the other units as well.

Note:

For wiring examples, refer to the separate manual “

Installation

examples for a DICN configuration

”.

Connection and setup of a DICN system

(See 

Annex I

"Installation examples for a DICN configuration" on

page 10

)

For a system with chillers in a DICN configuration, the chillers have to
be connected as shown in the figure below.

Make the connection as shown on the wiring diagram using an
AWG20/22 shielded cable, made up of a twisted pair plus shield.

Pay attention to the polarity! TX+ on one chiller must be connected to
TX+ on another chiller. The same for TX– and GND.

Setting the adresses on the digital controller

Set the addresses on the PCB by means of DIP-switches according
to the drawing below:

Where to find the DIP-switches of the digital controller

Important

Be sure to attach — in case of common leaving water control — the
optional temperature sensor.

Cable for remote digital controller

See remote digital controller in the operation manual.

1

A remote digital controller can be connected to the PCB inside
the unit by means of a 6-ray cable and a connector located on
the rear side of the remote digital controller in case you prefer to
operate the unit from a distance. You are allowed to use a cable
of up to 600 metres (EWLD120~260) or 300 metres
(EWLD340~540). Specifications of the cable: 6-ray telephone
cable with a maximum cable resistance of 0.1 

/m.

2

For units in a DICN configuration, the digital controllers of the
units can be installed remotely at a distance of up to 50 metres
by  using a 6-ray telephone cable with a maximum cable
resistance of 0.1 

/m.

Setting the adresses on the remote digital controller

When a remote digital controller is used, the adress has to be set by
means of DIP-switches according to the drawing below:

Where to find the DIP-switches of the remote digital controller

Master

Slave 1

Slave 2

Slave 3

PCB
address

Any unit can be master, slave 1, slave 2 or slave 3.

1

2

3

4

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

Master

Slave 1

Slave 2

Slave 3

Remote digital 
controller address

Any unit can be master, slave 1, slave 2, slave 3...

To  avoid damage to the controllers liquid crystals during
winter time, do not shut off the main power supply.

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...

Page 14: ...3 shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this...

Page 15: ...er circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerg...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22686 1...

Reviews: