Installation manual

9

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22686-1

Defining of the changeable digital/analog inputs and outputs

Besides locked inputs and outputs there are a number of changeable
inputs and outputs of which the function can be chosen from several
possibilities.

Possible functions for changeable digital inputs are:

: no function is appointed to the changeable digital input.

: no function is appointed to the changeable digital input,

but the input status can be read in the “input/output” menu.

 

: to switch between setpoints.

 

: to remotely switch the unit on or off.

   

:  to limit the capacity of the unit to the

entered values.

Possible functions for the changeable digital output are:

 

: no function is appointed to the changeable digital

output.

 

: no function is appointed to the changeable digital

output, but the output is closed.

 

:  can be used to steer a second evaporator

pump.

 

: indicates when the unit is working at 100%.

 

: to control a 3-way water valve when the unit is

working in free cooling state.

Possible configurations for the changeable analog input are:

: no function is appointed to the changeable analog input.

 

:

 

:

 

:

 

:

This allows the user to define a setpoint in function of an analog input
as mentioned above. Refer to 

"Defining the setpoint signal setting" on

page 9

.

   

: to control the leaving water temperature of

a DICN system.

Defining the setpoint signal setting

The setpoint signal is used to change the setpoint by an external
analog input signal on a stand alone unit or on Slave 1 in a DICN
system.

Example

Setting of the probe offset

It is possible to enter a correction value for certain measured
temperatures (inlet water evaporator temperature and mixed outlet
water evaporator temperature). This in order to correct a possible
measurement fault. The default value of the probe offset, is equal to 0.

Steering the pump manually

There is the possibility to turn the pump on or off manually. This
means that when the unit is off the pump can also be turned on at
any time to check the pump.

Defining the BMS settings

The BMS parameters allowing communication between the unit and
the supervisory system can be modified with the 

 

 and

the 

 

  screen of the service menu. The BMS

parameters are:

 

 screen:

 

:  if set to 

  (yes), the unit can be

commanded and configured from a supervisory system. If set to

  (no), the supervisory system can only read out values but

cannot modify them.

 

: used to address the PCB.

: indicates the communication protocol. If the optional

gateway is used to connect the units to a supervisory system,
the protocol is 

.

 

 screen:

 

: indicates the type of serial connection. The default

is set to 

!"

.

 

: indicates the speed of communication. The default

setting of 

# $%&

 must be used when the optional gateway

is connected.

Defining the thermostat settings

Defining the thermostat settings for inlet and outlet water temperature
of a, b and c can only be set in the service menu.

H

OW

 

TO

 

CONTINUE

After installation and connection of the packaged water-cooled water
chiller, the complete system should be checked and tested as
described in “Checks before initial start-up” in the operation manual
supplied with the unit.

Fill out the brief operation instructions form and fix it visibly near the
operating site of the refrigeration system.

in setpoints menu

in service menu


Remark

'  

 is only 

available when input 

 

 (

 or 

) is selected.

Result

Display in readout menu

A

at 0 V 

 12.0°C

  ( )

B

at 1 V 

 12.0°C + 5.0°C = 17.0°C

  ( *)

+   ( )

    ( )

  ( *)

  ( *)

,- .

 ( (  

'  ( ")

B

1 V

A

0 V

To define the thermostat settings of the
inlet water temperature.

,-  

(! (" ()

  (")

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...

Page 14: ...3 shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this...

Page 15: ...er circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerg...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22686 1...

Reviews: