Charging the unit

First perform a rough refrigerant charge according to the table:

VRC=volume of remote condenser (l)
LLP=length of liquid pipe (m)

Next perform a fine-tuning

If the liquid-line sightglass is showing seal after the rough
charging (due to possible different conditions), add 10%
refrigerant charge weight.

If the liquid-line sightglass is showing some gas-bubbles, the
rough refrigerant charge is sufficient by fine-tuning the additional
10% refrigerant charge weight.

If the liquid-line sightglass is showing flash gas, then charge
until one of the previous situations occur. Then fine-tune with the
additional 10% refrigerant charge weight. The unit must have the
time to stabelize which means that this charging has to be done
in a smooth way.

P

REPARING

CHECKING

 

AND

 

CONNECTING

 

THE

 

WATER

 

CIRCUIT

The units are equipped with a water inlet and water outlet for connec-
tion to a chilled water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.

1

Preparing the unit for connection to the water circuit

A box containing 

 couplings and a filter is delivered

with the unit.

As not to damage the parts of the units during transport, the water
inlet pipe with the flowswitch and the water inlet temperature sensor
and the water outlet pipe with the outlet water temperature sensor,
are not factory mounted.

Connecting the water inlet pipe containing the flowswitch and
inlet water temperature sensor: (not for EWLD120)
The water inlet pipe containing the flowswitch and inlet water
temperature sensor is mounted on the side of the water inlet of
the evaporator(s) and is pre-insulated.

Cut the tie wraps and fix the pipe with the supplied 
couplings to the evaporator inlet(s).

Connecting the water outlet pipe containing the outlet water tem-
perature sensor: (not for EWLD120)
The water outlet pipe containing the outlet water temperature
sensor is mounted on the side of the water outlet of the evapora-
tor and is pre-insulated.

Cut the tie wraps and fix the pipe(s) with the supplied 
couplings to the evaporator outlet(s).

After installation of the water inlet
and outlet pipes and as a general
rule for other units, it is recom-
mended to check the insertion depth
of the water temperature sensors into
the connection pipes prior to operation (see figure). 

refrigerant charge (kg)

40 HP

33+(VRC–40)x0.4+LLPx0.3

60 HP

67+(VRC–61)x0.4+LLPx0.5

80 HP

74+(VRC–91)x0.4+LLPx0.7

100 HP

70+(VRC–91)x0.4+LLPx0.7

Make sure that compressor load does not exceed
40% during rough charging of the unit.

You therefore best control the capacity on your
controller yourself by activating manual control mode
using the 

 

  screen of the user

settings menu.

For fine-tuning of the refrigerant charge, the compressor
must operate at full load (100%).

NOTE

Take  care for contamination of the remote condenser
in order to avoid blocking of the system. It is impossible
for Daikin to control the contamination of the "foreign"
condenser of the installer. The unit has a strict
contamination level.

NOTE

Use the liquid line check valve for charging refrigerant.

If air or dirt gets in the water circuit, problems may occur. 
Therefore, always take into account the following when
connecting the water circuit:

1.

Use clean pipes only.

2.

Hold the pipe end downwards when removing burrs.

3.

Cover the pipe end when inserting it through a wall so that
no dust and dirt enter

1

Water inlet of the evaporator

2

Flowswitch

3

Inlet water sensor

4

Water inlet pipe containing the flowswitch and the water inlet 
temperature sensor

5

 coupling

6

Counter pipe

7

Field water piping circuit

8

Filter

9

Filter end cap

Victaulic

®

1

5

6

7

8

4

3

2

9

5

5

5

Victaulic

®

Victaulic

®

Victaulic

®

 50 mm

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...

Page 14: ...3 shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this...

Page 15: ...er circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerg...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22686 1...

Reviews: