Installation manual

11

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22686-1

Example 2: Single ring system with separate pumps

Figure 2

  shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to deliver a constant water flow at a
constant temperature to a particular load. One unit, slave 3 (S3), is
kept as a standby unit.

Setup

The system is controlled on leaving water temperature. It is
required to install the additional sensor R8T (EKCLWS) in the
mixed water outlet and to connect it to the PCB of the master
unit.

Pump 1, pump 2 and pump 3 keep running as long as the
master unit, slave 1 or slave 2 are ON. Pump 4 only starts
running if slave 3 is switched ON. After switching OFF the units,
the pump runs for a time indicated by the 

 setting.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

  to

  using the dual setpoint selection switch S10S

which is connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

. In this

case, S6S (S3) has no function.

Example 3: Double ring system with several pumps

Figure 3

  shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to keep a buffer at a constant temperature
and to feed a load from this buffer. One unit, slave 3 (S3), is kept as a
standby unit.

Setup

The system is controlled on entering water temperature.

The pumps of the slave units only run when their compressor is
running (energy saving). the pump runs for a time indicated by
the 

 setting.

The pump of the master unit must run continuously so as to
sense the correct temperature.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

 

 to 

 

using the dual setpoint selection switch S10S which is
connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

. In this

case, S6S (S3) has no function.

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

The additional sensor R8T (EKCLWS) must be
connected directly to the PCB of the master unit.

Slave 3

Slave 2

Slave 1

Master

(

  

  

   (

 

       

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

 

 

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T–

R8T AI1

  

 

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

Slave 3

Slave 2

Slave 1

Master

(

  

   (

 

 

 

 

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

 

 

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T–

R8T AI1

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...

Page 14: ...3 shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this...

Page 15: ...er circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerg...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22686 1...

Reviews: