Installation manual

5

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22686-1

Connecting the filter

A field supplied blow down port for flushing fluid and accumu-
lated material from inside the filter can be connected on the filter
end cap.

Connecting the counter pipes
Weld the supplied counter pipes to the ends of the water circuit

and connect to the unit with the provided 

 couplings.

2

Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down. The drain plug is provided to drain the con-
denser. When doing this, also remove the air plugs (refer to the
outlook diagram).

3

Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing.

4

Shut-off valves should be provided at the unit so that normal ser-
vicing can be accomplished without draining the system.

5

Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.

6

For units in a DICN configuration with common leaving water
control, be sure to foresee an insertion hole for the additional
water temperature sensor. Sensor and sensor holder are
optional parts. 

The insertion hole shall be 1/4" GAS female thread and should
be located in the mixed waterflow of the chillers. 
Make sure that the sensortip is in the waterflow and that you
have a length of straight pipe (L) of at least 10x the pipe diame-
ter (A) before the sensor. 

Choose the position of insertion in a way that the cable length of
the sensor (12 m) is long enough to be attached to the master
PCB.

W

ATER

 

CHARGE

FLOW

 

AND

 

QUALITY

To  assure proper operation of the unit, the water flow through the
evaporator must be within the operation range as specified in the
table below and a minimum water volume is required in the system.

The minimum water volume v [l] in the system must fullfill the criteria
below:

The water quality must be in accordance with the specifications listed
in the table below.

The filter kit supplied with the unit must be
installed in front of the evaporator water inlet by
means of the supplied 

 couplings as

shown in the figure. The filter has holes of
diameter 1.0 mm and secures the evaporator
against clogging.

Improper installation of the supplied filter will
result in severe damage of the equipment
(freezing of the evaporator)

Victaulic

®

Victaulic

®

ØA

 5 x ØA

>30m

m

>3

0m

m

69m

m

69

m

m

>30m

m

69m

m

Minimum water flow

Maximum water flow

EWLD120

175 l/min

700 l/min

EWLD170

265 l/min

1070 l/min

EWLD240

350 l/min

1400 l/min

EWLD260

400 l/min

1600 l/min

EWLD340

525 l/min

2100 l/min

EWLD400

625 l/min

2500 l/min

EWLD480

700 l/min

2800 l/min

EWLD500

750 l/min

3000 l/min

EWLD540

800 l/min

3200 l/min

v>(Q/2)xt/(Cx

T)

Q

highest cooling capacity of the unit in lowest capacity step within 
the range of application (kW)

t

antirecycling timer of unit (AREC)/2(s)=300 s

C

specific heat capacity of the fluidum (kJ/kg°C)=4.186 kJ/kg°C for 
water

T

temperature difference between starting and stopping of the 
compressor.

T=a+2b+c

(for designation of a, b and c, refer to the operation manual)

NOTE

For units in a DICN configuration, the minimum
required water volume in the system must equal the
biggest required minimum volume of every individual
chiller in the system.

circulating 

water

supply 

water

tendency if 

out of criteria

Items to be controlled

pH

 at 25°C

6.8~8.0

6.8~8.0

co

scale

Electrical conductivity

[mS/m]

at 25°C

<40

<30

co

scale

Chloride ion

[mg Cl

/l]

<50

<50

corrosion

Sulfate ion

[mg SO

4

2–

/l]

<50

<50

corrosion

M-alkalinity (pH4.8)

[mg CaCO

3

/l]

<50

<50

scale

Total hardness

[mg CaCO

3

/l]

<70

<70

scale

Calcium hardness

[mg CaCO

3

/l]

<50

<50

scale

Silica ion

[mg SiO

2

/l]

<30

<30

scale

Items to be referred to

Iron

[mg

 

Fe/l]

<1.0

<0.3

co

scale

Copper

[mg Cu/l]

<1.0

<0.1

corrosion

Sulfide ion

[mg S

2–

/l]

not 

detectable

not 

detectable

corrosion

Ammonium ion

[mg NH

4

+

/l]

<1.0

<0.1

corrosion

Remaining chloride

[mg Cl/l]

<0.3

<0.3

corrosion

Free carbide

[mg CO

2

/l]

<4.0

<4.0

corrosion

Stability index

co

scale

The water pressure should not exceed the maximum
working pressure of 10 bar.

NOTE

Provide adequate safeguards in the water circuit to
make sure that the water pressure will never exceed
the maximum allowable working pressure.

Summary of Contents for EWLD120MBYNN

Page 1: ...INSTALLATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retagn...

Page 4: ...evaporator water down to 10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication EWLD120MBYNN EWLD260MBYNN EWLD480MBYNN EWLD170MBYNN EWLD340MBYNN EW...

Page 5: ...se radio interference in which case the user may be required to take adequate measures The units are designed for indoor installation and should be installed in a location that meets the following req...

Page 6: ...e performed and the air in the refrigerant piping must be evacuated to a value of 4 mbars absolute by means of a vacuum pump 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6...

Page 7: ...the supplied couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWLD120 The water outlet pipe containing the outlet water tem...

Page 8: ...listed in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes...

Page 9: ...on the unit the power circuit must be connected to the terminals 2 4 and 6 of the main isolator switch 2 Connect the earth conductor yellow green to the earthing terminal PE Interconnection cables Vol...

Page 10: ...erature sensor Cable for remote digital controller See remote digital controller in the operation manual 1 A remote digital controller can be connected to the PCB inside the unit by means of a 6 ray c...

Page 11: ...illed out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEFORE OPER...

Page 12: ...s inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe offset is equal to 0 Steering th...

Page 13: ...F all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the maste...