10
|
Configuration
Installer reference guide
185
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
In case of
Schedule only
or
Schedule + reheat
domestic hot water
preparation, the storage comfort temperature is weather dependent (according to
the weather dependent curve), the storage economic and reheat temperature are
NOT weather dependent.
In case of
Reheat only
domestic hot water preparation, the desired tank
temperature is weather dependent (according to the weather dependent curve).
During weather dependent operation, the end-user cannot adjust the desired tank
temperature on the user interface. Also see
145].
#
Code
Description
[5.C]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
WD curve
:
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E]
[0-0D]
▪
T
DHW
: The desired tank temperature.
▪
T
a
:
The
(averaged)
outdoor
ambient
temperature
▪
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
▪
[0-0D]: high outdoor ambient temperature:
10°C~25°C
▪
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: 45°C~[6‑0E]°C
▪
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
Margin
In domestic hot water operation, the following hysteresis value can be set for the
heat pump operation:
#
Code
Description
[5.D]
[6-01]
The temperature difference determining the heat
pump OFF temperature.
Range: 0°C~10°C
Example: setpoint (T
U
)>maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])