Piping installation
Installer reference guide
95
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
Piping length (m)
Minimum insulation thickness (mm)
<20
19
20~30
32
30~40
40
40~50
50
For other cases the minimum insulation thickness can be determined using the
Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool also calculates the maximum hydronic piping
length from the indoor unit to the outdoor unit based on the emitter pressure drop
or the other way around.
The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator
which can be reached via
https://professional.standbyme.daikin.eu
.
Please contact your dealer if you have no access to Heating Solutions Navigator.
This recommendation ensures good operation of the unit, however, local
regulations may differ and shall be followed.