6
|
Application guidelines
Installer reference guide
48
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
a
Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
b
Non-return valve (field supply)
c
Shut-off valve (field supply)
d
Auxiliary boiler (field supply)
e
Aquastat valve (field supply)
NOTICE
▪
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
▪
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
▪
Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
▪
Install non-return valves.
▪
An expansion vessel is already pre-mounted in the indoor unit. But for bivalent
operation, also make sure that there is an expansion vessel in the auxiliary boiler
loop. Otherwise when bivalent operation is running and if the Aquastat valve
would close, there would be no expansion vessel in the water circuit anymore.
▪
Install the digital I/O PCB (option EKRP1HBAA).
▪
Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See
"9.3.8 To connect the changeover to external heat
121].
▪
To setup the heat emitters, see
"6.2 Setting up the space heating/cooling
33].
Configuration
Via the user interface (configuration wizard):
▪
Set the use of a bivalent system as external heat source.
▪
Set the bivalent temperature and hysteresis.
▪
Set the operation mode to space heating only (no tank operation).
Changeover to external heat source decided by an auxiliary contact
▪
Only possible in external room thermostat control AND one leaving water
temperature zone (see
"6.2 Setting up the space heating/cooling system"
33]).
▪
The auxiliary contact can be:
-
An outdoor temperature thermostat
-
An electricity tariff contact
-
A manually operated contact
-
…
▪
Setup: Connect the following field wiring:
Summary of Contents for EPRA08EAV3
Page 289: ...13 13...
Page 290: ......
Page 291: ......
Page 292: ...4P634886 1 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...