10
|
Configuration
Installer reference guide
216
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2]
Space
heating/cooling
=0 (
Off
) and [C.3]
Tank
=0 (
Off
). See
216].
#
Code
Description
[9.P.5]
[7-0C]
Mixing valve turning time
: Time in
seconds for the mixing valve to turn from one
side to the other.
▪
20~300 sec (default: 125)
10.5.10 Commissioning
Overview
The following items are listed in the submenu:
A
Commissioning
User profile
Installer settings
Information
Operation
[A]
Commissioning
[A.1]
Operation test run
[A.2]
Actuator test run
[A.3]
Air purge
[A.4]
UFH screed dryout
About commissioning
10.5.11 User profile
[B]
User profile
"To change the user permission level"
B
User profile
Operation
Commissioning
Installer settings
Malfunctioning
10.5.12 Operation
Overview
The following items are listed in the submenu:
C
Operation
Malfunctioning
User profile
Commissioning
Room
[C]
Operation
[C.2]
Space heating/cooling
[C.3]
Tank
To enable or disable functionalities
In the operation menu, you can separately enable or disable functionalities of the
unit.
Summary of Contents for EPRA08EAV3