10
|
Configuration
Installer reference guide
168
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
#
Code
Description
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪
T
t
:
Target
leaving
water
temperature
(additional zone)
▪
T
a
: Outdoor temperature
▪
[0-07]: Low outdoor ambient temperature.
10°C~25°C
▪
[0-06]: High outdoor ambient temperature.
25°C~43°C
▪
[0-05]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water is required.
▪
[0-04]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
ambient
temperature.
[9‑07]°C~[9‑08]°C
Note:
This value should be lower than [0‑05] as
for high outdoor temperatures colder water is
required.
Emitter type
For more information about
Emitter type
155].
#
Code
Description
[3.7]
[2‑0D]
Emitter type
:
▪
0:
Underfloor heating
▪
1:
Fancoil unit
▪
2:
Radiator
The setting of the emitter type has an influence on the space heating setpoint
range and the target delta T in heating as follows:
Emitter type
Additional zone
Space heating setpoint
range [9‑05]~[9‑06]
Target delta T in heating
[1‑0C]
0:
Underfloor
heating
Maximum 55°C
Variable (see [3.B.1])
1:
Fancoil unit
Maximum 55°C
Variable (see [3.B.1])
2:
Radiator
Maximum 65°C
Fixed 10°C
Summary of Contents for EPRA08EAV3
Page 289: ...13 13...
Page 290: ......
Page 291: ......
Page 292: ...4P634886 1 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...