15
|
Disposal
Installer reference guide
258
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
Components
To activate/deactivate the recovery mode, you need the following components:
BS1
BS3
BS2
X1
X1
7‑LEDs display
BS1~BS3
Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:
#
Action
7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
1
Start from the default situation.
2
Press and hold
BS1
for 5 seconds.
3
Press
BS2
9 times.
4
Press
BS3
once.
5
Press
BS2
once.
6
Press
BS3
once.
7
Press
BS3
once.
The flashing H1P indicates the
recovery mode has been correctly
selected and is activated.
8
Press
BS1
once.
H1P keeps flashing, indicating that
you are in a mode that does not
allow compressor operation.
(a)
= OFF, = ON, and = flashing.
Result:
The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
Summary of Contents for EPRA08EAV3
Page 289: ...13 13...
Page 290: ......
Page 291: ......
Page 292: ...4P634886 1 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...