COMMISSIONING THE UNIT
AND THE INSTALLATION
7.1
Filling and air purge of unit and installation
7.1.1
CH system
1.
Insert the unit's plug into a socket.
The unit may carry out a self-check:
2
(on service display).
The unit will then go into the off setting:
-
(on service display) and the CH
pressure is shown on the temperature display.
In case of a CH pressure lower than 0.5 bar, the CH
pressure will be displayed flashing on the display.
In the off setting, the CH pressure will be displayed.
2.
Connect the filling hose to the fill/drain tap and fill the installation with clean drinking
water, up to a pressure between 1 and 2 bar if the installation is cold (to be read
from the temperature display).
3.
Aerate the system with the manual aerator (A).
Upon request, an automatic aerator can be fitted onto the unit instead of the manual
aerator.
4.
Aerate the installation with the manual aerators on the radiators.
5.
Top up the CH installation if the pressure has dipped too low due to the aeration.
6.
Check all couplings for leaks.
7.
Check whether the siphon is filled with water.
WARNING
If the siphon is not filled with water, combustion gases
may be released into the room.
WARNING
If an additive is added to the CH water, it must be
suitable for the materials used in the unit, such as
copper, brass, stainless steel, steel, plastic and rubber.
The additive should preferably have a KIWA/ATA/Atest
certification.
7.1.2
DHWprovision
1.
Open the main tap to bring theDHW section up to pressure.
2.
Aerate the exchanger and the pipe system by opening a DHW tap.
Leave the tap open until all air has flowed out of the system.
3.
Check all couplings for leaks.
7.1.3
Gas supply
1.
Aerate the gas pipe with the initial pressure measuring nipple (D) on the gas block.
2.
Check all couplings for leaks.
3.
Check the initial pressure and offset pressure (see par. 8.7).
Summary of Contents for EKOMB22AAV1H
Page 32: ...Daikin Europe NV 33...
Page 87: ...Daikin Europe NV 31...
Page 145: ...Daikin Europe NV 33...
Page 200: ...Daikin Europe NV 31...
Page 255: ...Daikin Europe NV 32...
Page 311: ...Daikin Europe NV 32...
Page 367: ...Daikin Europe NV 32...
Page 394: ...Daikin Europe NV 4 Daikin EKOMB22AAV1H EKOMB28AAV1H EKOMB33AAV1H CH DHW O...
Page 399: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 403: ...Daikin Europe NV 13 4 2 1 2 cm 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 404: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2 B...
Page 405: ...Daikin Europe NV 15 4 3 3 1 2 A B C 3 4 5 6 B 7 8 9 D E 10 D F 11 5 6 12 4 3 4...
Page 407: ...Daikin Europe NV 17 D CH A 55 C B X4 6 7 10 1 7 4 7 3 C o 0 3 P 5 2 3...
Page 414: ...Daikin Europe NV 24 5 7 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 421: ...Daikin Europe NV 31 5 10 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 422: ...Daikin Europe NV 32 5 10 6 C83 O A B EKOMB22AAV1H 100 m EKOMB28AAV1H 85 m EKOMB33AAV1H 80 m...
Page 429: ...Daikin Europe NV 39 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 431: ...Daikin Europe NV 41 30 C 90 C 80 C LED 40 C 65 C 60 C...
Page 439: ...Daikin Europe NV 50 8 3 8 3 1 8 3 2 8 3 3 CH OpenTherm 80 1 X2 24 V X4...
Page 442: ...Daikin Europe NV 53 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 13 9 1 2 1 2 3 4 5...
Page 447: ...Daikin Europe NV 58 11 Daikin Europe NV CH...
Page 448: ...008 1548599_05 05 2022 88551810...