6.10.5
Securing the flue system
IMPORTANT
•
These regulations are typical for both concentric and parallel flue
systems.
•
The flue system must be secured to a solid structure.
•
The flue system should have a continuous fall back to the boiler (1.5° to
3°). N.B. Wall terminals must be installed leveled..
•
Only use accompanying brackets.
•
Every elbow must be secured by using the bracket.
Exception at connecting on boiler:If the lenght of the pipes before and after
the first elbow, are no more than 250 mm, the second element after the
first elbow has to contain a bracket.
Note: The bracket must be positioned on the elbow!
•
Every extension must be secured per metre with a bracket.
This bracket must not be clamped around the pipe ensuring free
movement of the pipe..
•
Make sure bracket is locked into the correct position depending on the
position of the bracket on the pipe or elbow:
•
Do not mix flue parts or clamps of different suppliers.
Max. distance between clamps
Vertical
Others
2000 mm
1000 mm
•
Divide the lengths between the brackets evenly.
•
Every system must contain at least 1 bracket.
•
Position the first clam at a maximum of 500 mm from the boiler.
Summary of Contents for EKOMB22AAV1H
Page 32: ...Daikin Europe NV 33...
Page 87: ...Daikin Europe NV 31...
Page 145: ...Daikin Europe NV 33...
Page 200: ...Daikin Europe NV 31...
Page 255: ...Daikin Europe NV 32...
Page 311: ...Daikin Europe NV 32...
Page 367: ...Daikin Europe NV 32...
Page 394: ...Daikin Europe NV 4 Daikin EKOMB22AAV1H EKOMB28AAV1H EKOMB33AAV1H CH DHW O...
Page 399: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 403: ...Daikin Europe NV 13 4 2 1 2 cm 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 404: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2 B...
Page 405: ...Daikin Europe NV 15 4 3 3 1 2 A B C 3 4 5 6 B 7 8 9 D E 10 D F 11 5 6 12 4 3 4...
Page 407: ...Daikin Europe NV 17 D CH A 55 C B X4 6 7 10 1 7 4 7 3 C o 0 3 P 5 2 3...
Page 414: ...Daikin Europe NV 24 5 7 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 421: ...Daikin Europe NV 31 5 10 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 422: ...Daikin Europe NV 32 5 10 6 C83 O A B EKOMB22AAV1H 100 m EKOMB28AAV1H 85 m EKOMB33AAV1H 80 m...
Page 429: ...Daikin Europe NV 39 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 431: ...Daikin Europe NV 41 30 C 90 C 80 C LED 40 C 65 C 60 C...
Page 439: ...Daikin Europe NV 50 8 3 8 3 1 8 3 2 8 3 3 CH OpenTherm 80 1 X2 24 V X4...
Page 442: ...Daikin Europe NV 53 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 13 9 1 2 1 2 3 4 5...
Page 447: ...Daikin Europe NV 58 11 Daikin Europe NV CH...
Page 448: ...008 1548599_05 05 2022 88551810...