Daikin Europe NV
22
6.4
Connect room thermostat
6.4.1
Room thermostat on/off
1.
Connect the room thermostat (see par. 10.1).
2.
If necessary, set the feedback resistance of the room thermostat to 0.1 A. If unsure,
measure the electrical current and set it accordingly.
The maximum resistance of the thermostat pipe and the room thermostat amounts
to a total of 15 Ohm.
6.4.2
Modulating thermostat, Open Therm
The unit is suitable for connecting a modulating room thermostat, in accordance with
the OpenTherm communication protocol.
The most important function of the modulating room thermostat is to calculate the input
temperature at a required room temperature, in order to make optimal use of the
modulating. At every heating request, the required input temperature is shown on the
display of the unit.
Connect the modulating thermostat (see par.10.1).
If you want to use the tap water on/off switch function of the OpenTherm thermostat, the
tap water comfort function must be set to eco or on.
For more information, consult the manual of the room thermostat.
6.4.3
Modulating room thermostat, wireless
The EKOMB*AAV1H CH boiler is suitable to communicate wirelessly without
sending/receiving module with the Honeywell room thermostats T87RF1003 Round RF,
DTS92 and CMS927. The CH boiler and the room thermostat must be appointed to each
other:
•
Press the reset button of the unit for approximately 5 seconds in order to get to the
RF-
room thermostat menu.
•
One of the following codes will be shown on the display of the unit:
1.
rF
and
L /
-
: the display above the
button shows an
L
alternated by a
–
red led
: flashing
The CH boiler has not been appointed. A unit in this operating status, can be
linked by using the method of the appropriate room thermostat.
The method of appointment depends on the type of room thermostat and is
described in the installation and operating instructions of the wireless room
thermostat.
2.
rF
and
L / 1
: the display above the
button shows an
L
alternated by a
1
red led
: off
The CH boiler has already been appointed. There is already an existing link
with an RF room thermostat. In order to allow a new link to be made, the
existing link will have to be removed.
See:
Undo the appointment of an RF room thermostat to the CH boiler.
•
Press the reset button to leave the RF room thermostat menu or wait for 1 minute.
Testing the connection between the unit and the RF room thermostat
1. Press the reset button of the unit for approximately 5 seconds to access
the RF room thermostat menu of the boiler controller.
2.
Press the service
button
1x
. On the display above the
button, a
t
will be shown.
3.
Set the room thermostat to the test mode (see the installation and operating
instructions of the room thermostat).
4.
The
red led
above the reset button will flash if the appointment has
been carried out correctly.
5.
Press the reset button of the unit to exit the RF room thermostat menu of
the boiler controller. You will automatically exit the test mode 1 minute after
the last test message of the RF room thermostat has been received.
Summary of Contents for EKOMB22AAV1H
Page 32: ...Daikin Europe NV 33...
Page 87: ...Daikin Europe NV 31...
Page 145: ...Daikin Europe NV 33...
Page 200: ...Daikin Europe NV 31...
Page 255: ...Daikin Europe NV 32...
Page 311: ...Daikin Europe NV 32...
Page 367: ...Daikin Europe NV 32...
Page 394: ...Daikin Europe NV 4 Daikin EKOMB22AAV1H EKOMB28AAV1H EKOMB33AAV1H CH DHW O...
Page 399: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 403: ...Daikin Europe NV 13 4 2 1 2 cm 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 404: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2 B...
Page 405: ...Daikin Europe NV 15 4 3 3 1 2 A B C 3 4 5 6 B 7 8 9 D E 10 D F 11 5 6 12 4 3 4...
Page 407: ...Daikin Europe NV 17 D CH A 55 C B X4 6 7 10 1 7 4 7 3 C o 0 3 P 5 2 3...
Page 414: ...Daikin Europe NV 24 5 7 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 421: ...Daikin Europe NV 31 5 10 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 422: ...Daikin Europe NV 32 5 10 6 C83 O A B EKOMB22AAV1H 100 m EKOMB28AAV1H 85 m EKOMB33AAV1H 80 m...
Page 429: ...Daikin Europe NV 39 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 431: ...Daikin Europe NV 41 30 C 90 C 80 C LED 40 C 65 C 60 C...
Page 439: ...Daikin Europe NV 50 8 3 8 3 1 8 3 2 8 3 3 CH OpenTherm 80 1 X2 24 V X4...
Page 442: ...Daikin Europe NV 53 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 13 9 1 2 1 2 3 4 5...
Page 447: ...Daikin Europe NV 58 11 Daikin Europe NV CH...
Page 448: ...008 1548599_05 05 2022 88551810...