Daikin Europe NV
29
6.10
Connection to a sealed flue system.
6.10.1
Pipe lengths
As the resistance of the flue tube and air supply pipes increases, the power of the unit will
decrease. The maximum permitted power reduction is 5%.
The resistance of the air supply and the combustible gas outlet depends on the length, diameter
and all components of the pipe system. Per unit category, the total permitted pipe length has been
indicated for the air supply and the combustible gas outlet.
6.10.2
Permitted pipe lengths in concentric flue tube systems
Permitted pipe lengths when applying concentric 60/100
C13
C33
EKOMB22AAV1H
10 m
11 m
EKOMB28AAV1H
10 m
10 m
EKOMB33AAV1H
10 m
10 m
Permitted pipe lengths when applying concentric 80/125
C13
C33
C93
EKOMB22AAV1H
29 m
29 m
See par. 6.10.8
EKOMB28AAV1H
29 m
29 m
See par. 6.10.8.
EKOMB33AAV1H
29 m
29 m
See par. 6.10.8
Contact the manufacturer for test calculations for the resistance of the air supply and
combustible gas outlet pipe and the wall temperature at the end of the combustible gas
outlet pipe.
Replacement lengths
Bend 90°
R/D=1
2 m
Bend 45°
R/D=1
1 m
Knee 90°
R/D=0.5
4 m
Knee 45°
R/D=0.5
2 m
General assembly:
For all outlets, the following assembly applies:
1.
Slide the concentric combustion gas outlet pipe and air supply pipe.
2.
Slide the concentric pipes into each other.
From the unit, every pipe has to be slid into the previous one.
3.
Mount a non-vertical combustion gas outlet pipe on a slope towards the unit
(min. 5mm/m).
4.
Fit the assembly brackets in accordance with the assembly instructions of the supplier
of the air supply/flue tube system.
Summary of Contents for EKOMB22AAV1H
Page 32: ...Daikin Europe NV 33...
Page 87: ...Daikin Europe NV 31...
Page 145: ...Daikin Europe NV 33...
Page 200: ...Daikin Europe NV 31...
Page 255: ...Daikin Europe NV 32...
Page 311: ...Daikin Europe NV 32...
Page 367: ...Daikin Europe NV 32...
Page 394: ...Daikin Europe NV 4 Daikin EKOMB22AAV1H EKOMB28AAV1H EKOMB33AAV1H CH DHW O...
Page 399: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 403: ...Daikin Europe NV 13 4 2 1 2 cm 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 404: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2 B...
Page 405: ...Daikin Europe NV 15 4 3 3 1 2 A B C 3 4 5 6 B 7 8 9 D E 10 D F 11 5 6 12 4 3 4...
Page 407: ...Daikin Europe NV 17 D CH A 55 C B X4 6 7 10 1 7 4 7 3 C o 0 3 P 5 2 3...
Page 414: ...Daikin Europe NV 24 5 7 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 421: ...Daikin Europe NV 31 5 10 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 422: ...Daikin Europe NV 32 5 10 6 C83 O A B EKOMB22AAV1H 100 m EKOMB28AAV1H 85 m EKOMB33AAV1H 80 m...
Page 429: ...Daikin Europe NV 39 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 431: ...Daikin Europe NV 41 30 C 90 C 80 C LED 40 C 65 C 60 C...
Page 439: ...Daikin Europe NV 50 8 3 8 3 1 8 3 2 8 3 3 CH OpenTherm 80 1 X2 24 V X4...
Page 442: ...Daikin Europe NV 53 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 13 9 1 2 1 2 3 4 5...
Page 447: ...Daikin Europe NV 58 11 Daikin Europe NV CH...
Page 448: ...008 1548599_05 05 2022 88551810...