8 Configuration
Maximum tank temperature
The maximum temperature that users can select for the domestic hot
water. You can use this setting to limit the temperatures at the hot
water taps.
8.2.7 Contact/helpdesk number
8.3
Advanced configuration/optimization
8.3.1 Space heating/cooling operation: advanced
Preset leaving water temperature
You can define preset leaving water temperature temperatures:
Q
economic (denotes the desired leaving water temperature which
results in the lowest energy consumption)
Q
comfort (denotes the desired leaving water temperature
temperature which results in the highest energy consumption).
Preset values make it easy to use the same value in the schedule or
to adjust the desired leaving water temperature according to the
room temperature (see modulation). If you later want to change the
value, you only have to do it in one place. Depending on whether the
desired leaving water temperature is weather dependent or not, the
absolute desired leaving water temperature should be specified or
the desired shift values.
Temperature ranges (leaving water temperatures)
The purpose of this setting is to prevent selecting a wrong (i.e. too hot
or too cold) leaving water temperature. Thereto the available desired
heating temperature range and desired cooling temperature range
can be configured.
[A.4.3.2.2]
N/A
2 persons
The increment of the desired tank
temperature for 2 persons compared to 1
person. 0~20°C (default: 4°C)
[A.4.3.2.3]
N/A
3 persons
The increment of the desired tank
temperature for 3 persons compared to 2
persons. 0~20°C (default: 4°C)
[A.4.3.2.4]
N/A
4 persons
The increment of the desired tank
temperature for 4 persons compared to 3
persons. 0~20°C (default: 4°C)
[A.4.3.2.5]
N/A
5 persons
The increment of the desired tank
temperature for 5 persons compared to 4
persons. 0~20°C (default: 4°C)
[A.4.3.2.6]
N/A
6 persons
The increment of the desired tank
temperature for 6 persons compared to 5
persons. 0~20°C (default: 4°C)
INFORMATION
During disinfection of the domestic hot water tank, the tank
temperature can exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the
applicable legislation.
#
Code
Description
[A.4.5]
[6-0E]
Maximum setpoint
The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
If
Q
[E-07]=0: 40~80°C (default: 80°C)
(for EHBH in combination with
EKHW* cylinder)
Q
[E-07]=1: 40~60°C (default: 60°C)
(for EHVH in combination with
EKHW* cylinder)
The maximum temperature is NOT
applicable during disinfection function.
See disinfection function.
#
Code
Description
[6.3.2]
N/A
Number that users can call in case of
problems.
#
Code
Description
NOTICE
The preset leaving water temperature temperatures are
only applicable for the main zone, as the schedule for the
additional zone consists of On/OFF actions.
NOTICE
Select preset leaving water temperatures in accordance
with the design and selected heat emitters to ensure the
balance between desired room and leaving water
temperatures.
#
Code
Description
Preset leaving water temperature for the main leaving water
temperature zone in case of NOT weather dependent
[7.4.2.1]
[8-09]
Comfort (heating)
[9-01]~[9-00] (default: 45°C)
[7.4.2.2]
[8-0A]
Eco (heating)
[9-01]~[9-00] (default: 35°C)
[7.4.2.3]
[8-07]
Comfort (cooling)
[9-03]~[9-02] (default: 15°C)
[7.4.2.4]
[8-08]
Eco (cooling)
[9-03]~[9-02] (default: 20°C)
Preset leaving water temperature (shift value) for the main leaving
water temperature zone in case of weather dependent
[7.4.2.5]
N/A
Comfort (heating)
–5~+5°C (default: 0°C)
[7.4.2.6]
N/A
Eco (heating)
–5~+5°C (default: –3°C)
[7.4.2.7]
N/A
Comfort (cooling)
–5~+5°C (default: 0°C)
[7.4.2.8]
N/A
Eco (cooling)
[–5~+5°C (default: +3°C)
NOTICE
In case of a floor heating application it is important to limit
the:
Q
maximum leaving water temperature at heating
operation according to the specifications of the floor
heating installation.
Q
the minimum leaving water temperature at cooling
operation to 18~20°C to prevent condensation on the
floor.