08 + ERLQ004~008
Daikin Altherma - Low Temperature Split
4P313774-1 – 2012.05
Installer reference guide
44
8 Configuration
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1
installed in the room, 1 installed at the
indoor unit):
User interface location:
Q
At unit: the other user interface is
automatically set to In room and if
RT control is selected act as room
thermostat.
Q
In room(default): the other user
interface is automatically set to At
unit and if RT control is selected to
act as room thermostat.
#
Code
Description
[A.2.1.8]
[7-02]
The system can supply leaving water to
up to 2 water temperature zones. During
configuration, the number of water zones
must be set.
Number of LWT zones:
Q
0 (1 LWT zone)(default): Only 1
leaving water temperature zone.
This zone is called the main leaving
water temperature zone.
Q
Q
1 (2 LWT zones): 2 leaving water
temperature zones. The zone with
the lowest leaving water
temperature (in heating) is called
the main leaving water temperature
zone. The zone with the highest
leaving water temperature (in
heating) is called the additional
leaving water temperature zone. In
practice, the main leaving water
temperature zone consists of the
higher load heat emitters and a
mixing station is installed to achieve
the desired leaving water
temperature.
#
Code
Description