5.5.1
64B
These are sequence input signals that control the operations of this unit from an external device.
Connect them as necessary by following the information below.
Terminal Name
Signal Name
Remarks
COM2
Digital input common
Can be either positive or negative
DIN0
Digital input 0
Start/stop signal (At shipment from factory: Start when OFF/stop
when ON)
DIN1
Digital output 1
(Reserved) (Do not connect.)
DIN2
Digital output 2
(Reserved) (Do not connect.)
CAUTION
Prepare an external power supply that is DC24 V 10%/0.5 A minimum.
It is not possible to supply power from this controller to external destinations.
The current flowing to each input circuit is 5 mA (typ.). If a circuit is configured with contacts, etc., pay
attention to the minimum current for those contacts, etc.
Internal circuit
DIN0
DIN1
DIN2
COM2
5 mA
External power
supply
DC24 V