Panel
Indication
Code
Name
Operation Range
Default
Value
Details
P02
T_SW
Pressure
switch output
delay time
0.00 to 9.99 [sec]
0.00
Sets the delay time from when the pressure
P03
PSW
H
Pressure
switch
indication
retention
setting
0 to 2
0
When the
displayed on the operation panel can be
retained. It is also possible to record the
the alarm history, although it is not usually
recorded there.
Value
L63 Indication
Retention
Recording in
Alarm History
0
Not retained
No recorded
1
Retained
No recorded
2
Retained
Recorded
P04
DS_P
Pressure unit
selection
setting*
0: MPa indication
1: PSI indication
0
Enables selection of the display unit for
pressures displayed on the panel.
P09
INIF
Initialize to
defaults
0: Disable
1: Initialize P00 to P09
2: Initialize all parameters
0
and back on initializes parameters to their
default values according to the setting made.
P10
L_TI
PQ integration
time correction
factor
1 to 500 [%]
100
Sets the integration time correction factor for
PQ control. The smaller the value, the faster
the response, but the more surge pressure
occurs. Enabled when
P13
PL.0
Pressure
setting
4 MPa
specifi
cations
1.5 to 4.0
[MPa]
1.5
Sets the target pressure.
22 to 58
[×10 PSI]
58
7 MPa
specifi
cations
1.5 to 7.0
[MPa]
1.5
22 to 101
[× 10 PSI]
101
QL.0
Flow rate
setting
14 L
specifi
cations
2.5 to 15.2
[L/min]
15.2
Sets the target flow rate.
25 L
specifi
cations
3.5 to 25.1
[L/min]
25.0
30 L
specifi
cations
3.5 to 28.5
[L/min]
28.5
P31
P_SN
Pressure
sensor rated
value
1 to 35 [MPa]
10
Sets the rated pressure of the pressure
sensor. Normally, this setting does not need to
be changed.
P32
S_TM
Surgeless start
time
0.01 to 9.99 [sec]
0.50
Sets the start-up time for a start with the motor
at a stop.
Increasing the value makes the start-up
smoother and can prevent start-up surge, but
it lengthens the response time at start-up.