Connect the power cable to the terminal block.
The recommended tightening torque is 1.0 N m.
The screw for connecting the 200 V specification power supply ground is different from those for the
power supply cable connection terminals, so take care not to confuse them.
DANGER
Use an AC
Use a cable appropriate for the power supply capacity.
Connect the end of the cable by using a crimp terminal. Use a tool suited to crimp
terminals. Faults may result in the cable coming loose during use, short-circuiting
accidents, and burnout due to abnormal heat generation.
Do not use anything other than the terminals provided with this product for connecting
the power supply.
Use an M4 cross-recessed pan-head screw with washer assembly, 8 mm long, for the
power supply ground terminal.
Be sure to ground ground terminals in accordance with the law in the country
concerned. Make a direct connection without going through a circuit breaker.
Do not connect the power supply cable to the input/output signal terminals or ground
terminal. This could cause an electric shock or equipment damage.
This product incorporates an overcurrent protection function internally, so no thermal relay for overcurrent protection
is necessary.
Press in the direction
shown by the arrow
with a screwdriver.
Press the lever with a screwdriver to open the top
shutter, then insert the cable.
From left, ground L1, L2, L3
Power supply connection terminal
From left: L1, L2, L3
Power supply cable port
23 hole
Shutter opens.
Lever
Grounding connection
Terminal block securing screws
Do not use these for power
supply connection.
Control power supply connection
From left: L1C, L2C
(effective when option selected)