Verify that no ERROR number is shown on the screen (see section DZK
and
section
Errors in Wired and Wireless Thermostats
17B
The damper-modulating functionality does not work as expected
1
Verify that the damper REG level is located as configured in the
18B
In Heat mode, when trying to change to Cool mode, the thermostat returns to Heat mode
1
The operation mode in the installation is controlled by the Daikin master indoor unit. The
operation mode can only be changed from the DZK Main Wired thermostat connected to Daikin
master indoor unit.
19B
In Heat Pump installations, the DZK zoning box connected to a slave indoor unit,
changes to Stop mode
1
This is caused by the incompatibility between the subordinate unit mode and the master unit.
Check the master unit is not operating in Fan mode (see User manual).
20B
Defrost mode on the indoor unit don’t work properly
1
If the Daikin indoor unit has start/stop cycles in periods shorter than 30 minutes, set the dip
switch #2 in the DZK Interface Board to ON.
21B
The DZK system does not detect the DZK BACnet Interface
1
Verify that the LED D9 is blinking and LEDs D7 and D8 are alternately blinking (see section
BACnet Interface auto diagnosis
If the above is not displayed, check the correct connection of the gateway on the DZK Control
Board, verifying the 4-pin connector.
22B
The Interface for use in BACnet cannot be connected
1
Verify that LEDs situated on the Ethernet connector
) are blinking, and those in the Ethernet connector are active. If the above is not true,
check that the Ethernet cable is properly connected
23B
The indoor unit starts with the system set on off (off or user mode on Stop)
1
Verify that the Setback field setting on the Daikin indoor unit is disabled (see section
Interface Board, Connection and configuration
Summary of Contents for DZK Series
Page 1: ...Installation Manual Zoning Kit ...
Page 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Page 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Page 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Page 55: ......
Page 56: ...Phone 855 770 5678 http www daikinac com 400886 ...