Zone Parameters
Linked Zones.
Displays the linked zones and allows you to select
the secondary control dampers associated with the thermostat.
Thermostat Type.
Configure the thermostat as Main or Zone.
Menu Mode.
The thermostats can be set in Basic or Advanced mode
(Advanced by default). When set to Basic mode, the user can control
the following parameters: On/Off, set point, local ventilation and
user settings.
Offset.
This option allows the user to apply an offset to the room
temperature reading. The offset range goes from -5 to 5˚F (-2.5 to
2.5˚C). The default value is 0˚F/ 0˚C. This offset will always be applied
to the measured room temperature of the zone.
User Mode Setpoint.
This option is used to configure the set point
temperature of each user mode for each zone.
-
Comfort.
Heating mode: 59 to 86˚F/ 15 to 30˚C, by default
68˚F / 20˚C. Cooling mode: 64 to 86˚F/ 18 to 30˚C, by default
75˚F / 24˚C.
-
Eco.
Heating mode: 59 to 86˚F / 15 to 30˚C, by default 66˚F /
19˚C. Cooling mode: 64 to 86˚F / 18 to 30˚C, by default 84˚F /
29˚C.
-
Unoccupied.
Heating mode: 59 to 72˚F/ 15 to 22˚C, by
default 63˚F/17.5˚C. Cooling mode: 75 to 86˚F/ 24 to 30˚C, by
default 81˚F/27˚C.
-
Vacation.
Heating mode: 50 to 61˚F/ 10 to 16˚C, by default
50˚F/10˚C. Cooling mode: 84 to 96˚F/ 29 to 35.5˚C, by default
95˚F/35˚C.
Weight.
This option is used to set the weight of each zone for
purposes of determining system operation. The weight of the zone
will be used for calculating the mode (auto-change over) or for
calculating heat demands when using auxiliary heat. It is an
indicator of the size / importance of the zone. Possible values range
from 0-100. By default, the weighting is set to Auto and each zone's
weight is automatically generated based on the number of zones.
For example, if there are four zones, each zone's weight is
automatically set to 25.
If this option is disabled, the weight of the zone can be set manually.
Note:
it cannot be configured as
Main if there is already another
Main thermostat.
Summary of Contents for DZK Series
Page 1: ...Installation Manual Zoning Kit ...
Page 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Page 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Page 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Page 55: ......
Page 56: ...Phone 855 770 5678 http www daikinac com 400886 ...