29
Installation Manual
Rev. 2.00
Date 01-2019
Note:
when the radio channel is
opened, it will remain open for 15
minutes.
•
Run For (min).
Configure the time duration that ventilation is
activated (in minutes). Configurable from 5 to 20 minutes, in 5
minutes increments (by default, 10 minutes).
Type of Opening.
This menu allows you to enable or disable the
modulating system dampers. Proportionally graduated in four
steps, the opening or closing of the damper is based on the demand
for zone temperature to adjust the flow rate. By default, the dampers
are set for Modulating.
If you select the Modulating option, select the desired damper and
set the REG lever position, where position I is completely open and
position IV has the smallest opening.
Radio Channel.
This option allows you to open the wireless channel
association for connecting Wireless and Wireless Lite Thermostats to
the Zoning box control board. By default, the radio channel is
closed.
Supply Temperature.
This option allows the system demand to be
ignored if the supply temperature exceeds a certain limit. The
selectable heating cut out temperatures are 100-114-129-143-158˚F
(38-46-54-62-70˚C). By default, the system will stop heating if the
supply temperature reaches 129˚F / 54˚C.
Away Mode Settings.
This option configures the following
parameters of the unoccupied user mode and the vacation user
mode:
-
Hysteresis.
If the set point temperature is surpassed by the
differential defined, the zone will cease demand. Range: 2 to
7˚F / 1 to 3.5˚C in steps of 1˚ / 0.5˚C. By default, 6˚F / 3˚C.
-
Override Time.
Sets time that the zone will resume the
selected away mode when the user touches the thermostat
screen during an away period. Values: 10 to 120 minutes in
steps of 10 minutes. By default, 60 minutes.
Summary of Contents for DZK Series
Page 1: ...Installation Manual Zoning Kit ...
Page 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Page 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Page 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Page 55: ......
Page 56: ...Phone 855 770 5678 http www daikinac com 400886 ...