13
Installation Manual
Rev. 2.00
Date 01-2019
Keep in mind:
make sure that
the zoning box is in its correct
position. (Actuators at the
bottom)
If upon receiving the unit it is determined that one of the outlets will not
be used, take the following actions:
1.
Install the unit and wiring required to start with the Wired
Thermostat configuration. The unit should have all dampers open.
2.
Configure the Wired Thermostat. Once the thermostat is assigned
to a zone, all other dampers will close except for the zone that is
assigned to the Main Wired Thermostat.
3.
At this time, disconnect the motor cable from the outlet that will
not be used.
4.
Permanently seal the outlet using the supplied plug and follow the
local installation recommendations.
DZK ZONING BOX
Dampers are numbered starting with number 1 next to the Zoning box
control board.
Assembly
The Zoning Box allows for a fast and simple connection to Daikin indoor
units FBQ_P, FMXQ_P and FXSQ_T.
Follow the steps listed below to make an easy and reliable DZK installation:
Models
Damper Size
Number of
Dampers
FXSQ 15 TAVJU
FDMQ09-12RVJU
6”
4
8”
3
FBQ 18 - 24 - 30 PVJU
FXMQ 15 - 18 – 24 PBVJU
FXSQ 18-24-30 TAVJU
FDMQ15-24RVJU
6”
5
8”
4
FBQ 36 - 42 PVJU
FXMQ 30 - 36 - 48 - 54 PBVJU
FXSQ 36-48 TAVJU
6”
6
8”
4
Summary of Contents for DZK Series
Page 1: ...Installation Manual Zoning Kit ...
Page 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Page 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Page 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Page 55: ......
Page 56: ...Phone 855 770 5678 http www daikinac com 400886 ...