17
Installation Manual
Rev. 2.00
Date 01-2019
beginning with the central damper opening and ending with
damper
No.
1
(Closest to the zoning box control board). The
reduced flow in the central dampers will increase the flow of the
dampers at the ends.
•
The use of an anemometer verifies that the flow in each grille
is within the installation requirements.
Minimum Air (A-M)
Similarly, the zoning box allows a minimum air opening for each
damper, if needed. By default, the
Position a
damper is configured
in the full-close position. To adjust minimum air for any damper,
proceed as follows:
•
Check that the dampers are wide open. To do so, set the
system to Stop user mode, from the Main Wired Thermostat.
•
Perform the setting of the dampers by changing the lever
A-M position beginning with the central damper opening of
the box and ending with damper
No. 1
. (Closest to the
zoning box control board).
•
With the damper open, place the handle A-M in the desired
open position. It has 4 positions (a, b, c and d) where position
“a" is fully closed and is "d" is the fully open.
•
The use of an anemometer verifies that the flow in each grille
is within the installation requirements.
A-M lever