48
Installation Manual
Rev. 2.00
Date 01-2019
4
Restart the zone and re-associate it with the system. To do this, press and hold on
and
restart the start-up configuration process.
Keep in mind:
To associate the thermostat, first open the association radio channel pressing the
SW1 at the DZK Control Board or from any Wired Thermostat, activating the
Radio channel
parameter inside
Advanced Settings, system parameter.
5
Restart system: If the system is restarted, this error may be displayed in the thermostats at the
beginning of the process. This message should disappear after around 30 seconds.
2B
Error 5 -
Temperature sensor is open
The zone ceases to measure the room temperature, therefore the zone cannot generate demand.
Replace the device.
3B
Error 6 -
Temperature sensor is short circuited
The zone ceases to measure the room temperature, therefore the zone cannot generate demand.
Replace the device.
4B
Error 8 (Wired Thermostat) -
Wireless Lite Thermostat not found
The zone ceases to measure the room temperature of an associated Wireless Lite Thermostat, therefore
the zone cannot generate demand. Check which Wireless Lite Thermostat is not working properly. To
solve this incident check:
1
Power supply: Check the battery and replace it if necessary.
2
Verify the thermostat microswitch corresponds with the zone associated. If not, activate it
using the tab with the value needed.
Keep in mind:
To associate the thermostat, first open the association radio channel pressing
the SW1 at the DZK Control Board or from any Wired Thermostat, activating the
Radio channel
parameter inside
Advanced Settings, system parameter.
Summary of Contents for DZK Series
Page 1: ...Installation Manual Zoning Kit ...
Page 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Page 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Page 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Page 55: ......