Installation Manual 3P581074-1D
DGE601A51/DGE602A51
61
English
5.3
Setting address on the outdoor unit
Setup on the outdoor unit
To use the DGE601A51, you need to set an Airnet address for the outdoor unit.
Also, you need to set a demand address and enable demand setting if necessary.
To set the address of an outdoor unit, you can use the push buttons located on the unit’s
printed circuit board.
The current setting or operating status of an outdoor unit is indicated by the outdoor unit’s
LED or segment display.
For details, refer to the service manual of the air conditioner.
<LEDs (segment) and setting switches for each mode>
Display of each mode
setting switch
Display of each mode
(LED/Segment)
Outdoor unit with LED display
Outdoor unit with segment
display
Lit
Unlit
5.3.1
Steps for setting the outdoor unit Airnet address
If you cannot set the outdoor unit Airnet address with the remote controller, follow the
procedure below to perform setting.
1. Press the
BS1
button for 5 seconds or more.
The LEDs and segments will be in the state shown below.
LED (segment) display
Outdoor unit of the LED display
Outdoor unit of the
segment display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
SEG1
SEG2
SEG3
2
0
0
2. Press the
BS2
button 13 times. (Select the setting value.)
3. Press the
BS3
button.
You can now find out the current AIRNET address setting by the LED (segment).
4. Press the
BS2
button to change to any Airnet address.
(Set the Airnet address number within the range of 1 to 63.)
5. Press the
BS3
button 2 times to confirm the AIRNET address setting.
6. Press the
BS1
button 1 time to return to the normal mode.
01_EN_3P581074-1D.indd 61