22
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
English
NOTE
• What’s a remote controller group?
1 remote controller can simultaneously control a maximum of 16 indoor units.
This capability is referred to as group control. A remote controller group is a group of
indoor units controlled under the same remote controller.
<Schematic drawing of a remote controller group>
F1, F2 P1, P2
F1, F2 P1, P2
F1, F2 P1, P2
F1, F2 P1, P2
A
A
Max. 16 indoor units
NOTE
<DIII-NET connecting>
• When Connecting multiple wires to the termi
nal of DIIINET
Connecting multiple wires to 1 terminal on the
DGE601A51 terminal block is not possible.
If you want to connect multiple wires, connect
the mark (F1 or F2) you want to connect to the
terminal with the same mark as shown in the
figure on the right.