28
Installation Manual 3P581074-1D
DGE601A51/DGE602A51
English
3.4.2
Wiring specifications
•
Cable type: CPEV cable, FCPEV cable, CVV(S) cable
• Core thickness: CPEV cable, FCPEV cable:
φ
0.65 0.9 mm
CVV(S) cable: 0.75 - 1.25 mm²
• Cable length: 200 m or less
<Pulse width>
A
B
A
Pulse width: 20 to 400 ms
B
Pulse interval: 100 ms or more
CAUTION
•
The contact connected to the contact input terminal must be capable of han
-
dling 10 mA at 16 V DC.
•
If an instantaneous contact is used for triggering an emergency stop, use one
that has an energisation time of 200 ms or more.
NOTE
Once the emergency stop input signal is turned on, all air conditioners stop and do not
restart until the emergency stop input is cleared.