Installation Manual 3P581074-1D
DGE601A51/DGE602A51
37
English
5
Setting addresses for each air conditioner
The
“DIII-NET system”
makes use of
“DIII-NET addresses”
, unique control addresses
used to identify each air conditioning group that is part of the system.
You set
“DIII-NET addresses”
manually with the remote controller of the air conditioners.
There are several remote controller types, and the setting method differs depending on
the type. This section describes the two most commonly used types of remote controller.
5.1
Setting addresses with wired remote controller (BRC1H*)
This section describes wired remote controller BRC1H*.
NOTE
For how to set addresses for ventilation equipment (Heat Reclaim Ventilation units) and
various adaptors, refer to their respective documentation.
Names of buttons
Below are the names of the buttons and display of wired remote controller (BRC1H*).
A
ON/OFF
Turn ON/OFF the system.
B
ENTER/ACTIVATE/SET
• From the homescreen, enter the main menu.
• From the main menu, enter one of the submenus.
• From their respective submenu, activate an opera
tion/ventilation mode.
•
In one of the submenus, confirm a setting.
C
CYCLE/ADJUST
• Cycle left.
•
Adjust a setting (default: decrease).
D
CYCLE/ADJUST
• Cycle right.
•
Adjust a setting (default: increase).
+
-
A
C B D
The operation procedure of the wired remote controller is as follows.
The operation steps will be explained in the following order.
“Remote controller group
MAIN”
,
“Remote controller group SUB”
,
“Indoor unit Airnet address”
,
“Outdoor
unit Airnet address”
.
NOTE
You cannot perform the following procedure when the display backlight is off.
In this case, press any key to turn on the backlight before starting the procedure.