Timing of E-mail Sending
Referring to the figure below, timing of sending e-mails is described.
[Send when a malfunction occurs in the normal state]
If a malfunction occurs in the destination groups defined in the e-mail sending,
wait
three minutes
from the malfunction (
q
in the figure below) before sending an e-mail.
* An e-mail will not be sent immediately after the first malfunction.
During the waiting time of three minutes, if another malfunction occurs in different
groups (
w
or
e
in the figure below), one e-mail containing such multiple malfunctions
will be sent.
[Resend after sending once]
As shown in case of
Group B
, if the malfunction persists even after the sending time
interval from the first mail sending has elapsed, another e-mail will be sent.
In the group for which the e-mail has been sent, after recovering from the malfunction,
if another malfunction occurs again (
t
in the figure below), the latest malfunction will
be sent after the sending time interval will have elapsed.
During the sending time interval, if a new malfunction occurs (
r
in the figure below),
an e-mail will be sent after the sending time interval will have elapsed.
When the sending time interval has elapsed, if no malfunction is found in the groups,
the system will move from the resend state to the normal state.
* : The mark represents occurrence of a malfunction and the mark
represents recovery from the malfunction.
Operation
(Reference)
Description
55
Alarm E-mail
* The e-mail
function is
included in
an option
sold
separately,
where
combined
with the Web
function.
Group B
Group D
Send the malfunctions
occurred in Group A, B, C
Normal
state
Normal
state
Resend state
3 minutes from
occurrence of
the malfunction
(wait for sending)
i
Figure : Timing of E-mail Sending
Group A
1
2
5
Sending time
interval
Group C
4
3
If no malfunction is
found, the system
will send no e-mail
and go back to the
normal state to start
monitoring the
air conditioning unit.
Sending time
interval
Send the malfunctions
occurred in Group B, C, D
Group B : The malfunction
persists.
Group C : The malfunction has
occurred again.
Group D : Another malfunction
has occurred.