• Control systems
• Standard protocol interfaces • BACnet Interface
Communications Check Sheet
BACnet object list
Memner
number
Name
Object name
(XXX: Air Con Logical Group Number)
Object type
Unit
Inactive
Active
Text-1
Text-2
Text-3
Text-4
1
Start/stop (setting) (Note 2)
Start stop command_XXX
BO
Stop
Operation
2
Start/stop (status)
Start stop status_XXX
BI
Stop
Operation
3
Alarm
Alarm_XXX
BI
Normal
Malfunction
4
Malfunction code
Malfunction code_XXX
MI
Normal
Manufacturer specific
5
Air conditioner mode (Setting) (Note 2)
AirConModeCommand_XXX
MO
Cooling
Heating
Fan
Auto
6
Air-conditioning mode (status)
AirConModeStatus_XXX
MI
Cooling
Heating
Fan
7
Air flow rate level (setting) (Note 2)
Air flowRate command_XXX
MO
Low
High
8
Air flow rate level (status)
AirFlowRateStatus_XXX
MI
Low
Gigh
9
Measured room temperature (Note 1)
Roomtemp_XXX
AI
°C
10
Set room temerature (Note 2)
TempAdjust_XXX
AV
°C
11
Filter sign signal
FilterSign_XXX
BI
No
Yes
12
Filter sign segnal reset
FilterSignReset_XXX
BV
Reset
13
Remote control enable /
disable (start / stop)
RemoteControlStart_XXX
BV
Enabled
Disabled
14
Remote control enable / disable
(air-conditioning mode)
RemoteControlAirConModeSet_XXX
BV
Enabled
Disabled
15
Blank
16
Remote controller enable /
disable (set temperature)
RemoteControlTempAdjust_XXX
BV
Enabled
Disabled
(*)17
Central control ‘lower
central control disable)
CL_Rejection_XXX
BV
Enabled
Disabled
18
Blank
19
Accumulated power
ElecTotalPower_XXX
BV
Enabled
Disabled
20
Communication status
CommunicationStatus_XXX
BI
Normal
communication
Communication
error
(*)21
Forced system stop
SystemForcedOff_XXX
BV
Clearance
Forced stop
22
Air direction (setting) (Note 2)
AirDirectionCommand_XXX
AV
23
Air direction (status)
AirDirectionStatus_XXX
AI
24
Forced thermostat disble (setting)
ForcedThermoOFFCommand_XXX
BO
Clearance
Set
25
Forced thermostat disable (status)
ForcedThermoOFFStatus_XXX
BI
Clearance
Set
26
Energy saving (setting)
Energy EfficiencyCommand_XXX
BO
Clearance
Set
27
Energy saving (status)
EnergyEfficiencyStatus_XXX
BI
Clearance
Set
28
Thermostat status
ThermoStatus_XXX
BI
OFF
ON
29
Compressor status
CompressorStatus_XXX
BI
Stop
Operation
30
Indoor fan status
IndoorFanStatus_XXX
BI
Stop
Operation
31
Heater operation status
HeaterStatus_CCC
BI
Stop
Operation
Central control (lower central control disable) and orced systemm stop are obly available for 000, 064, 128, and 192.
Notes
1 The room temperature is measured with the suction air. Since the indoor unit fan stops when the thermostat is disabled or the
air conditioner is stopped, or in z special operation such as defrosting, temperature measurement may be affected by the heat
exchanger, and may detect and transmit a different temperature from the actual room temperature, For this reason, this value should
be considered as a reference for the room temperature.
If the building management system manufacturer uses this value for system control (e.g., switching the airconditioning mode or
preset temperature), the manufactureer must take on the whole responsibility.
2 The air conditioner saves the settings for the temperature, start/stop status, air-conditioning mode, air direction, and air flow rate in
the nonvolatile memory each time they are changed, so that the settings will not be lost when a power cut occurs. This nonvolatile
memory has a write count limit and may cause a failure if it is written exceeding the limit count.
Therefore when the temperature, start / stop status, air-conditioning mode, air direction, and air flow rate of each indoor unit are
automatically controlled from the central monitoring panel, be sure that the number of changes for each setting
should not exceed
7,000 timer per year.