102
• Control systems
• intelligent Touch Manager • ED721208
The figure below shows the PC board built in this equipment.
H4P
H12P
3
7
2
6
8
5
1
4
3
2
1
8
4
7
6
5
1
4
2 3
DS6
DS2
DS3
DS4
DS5
SS1
0
D2
CD
D3
D1
D4
CA
A4
M1
A3
CM
A2
A1
M4
M3
M2
F2
F1
N
L
H1P H2P H3P
H10P
4
1 2
H9P
H11P
3
X1M
X2M
X3M
TNc2
HAP
TNa1
HAP
TNb4
RED
TNc1
TNa3
TNc4
GRN
TNc3
X1A
YE
TNb3
LED10
H10P
TNa4
RED
AC200V
~240V
TNb1
TP1
TNa2
X4M
TNb2
X2A
Power supply terminal block
(L, N)
Transmission error monitor
(LED10: Red)
Micro-computer OK monitor
(LED-A: Green)
Quantity change shortcircuit pin
(TP1)
Start error masks switch (DS6-1)
Error detecting switch (DS6-2)
Terminal block for control output
(Terminal size: M3.5)
Terminal block for monitor input
(Terminal size: M3.5)
Output selector switch (SS1)
Monitor input switch (DS6-3)
Forced stop switch (DS6-4)
Start / Stop error switch (DS4-4)
Later push priority switch (DS4-3)
Transmission error switch (DS4-2)
Momentary stop auto switch (DS4-1)
Abnormal input detecting switch (DS2)
Terminal block for transmission (F1/F2)
(Terminal size: M3)
Transformer connecting connector
(CN1/CN2)
DIII-NET Address No. setting switch
(RS1/DS1)
Switch for selecting the number of
facility equipment connected (DS3)
Abnormal output cutoff / hold switch
(DS5)
For the power supply, use
1 ~ 200 - 240V.
When the transmission is
abnormal, the lamp lights up,
disabling remote control. (The
lamp goes out in the normal
condition.)
When the micro-computer is in
normal operation, the lamp flickers.
Shortcircuit during control quantity
setting
It is possible to select whether the
error at startup is masked for 10 or
30 seconds.
It is possible to select whether the
equipment connection error is a non-
latch or latch error.
The start / stop signal is outputted to
the equipment to be connected
The facility equipment status is
monitored.
This switch makes it possible to select continuous 1
output or instantaneous 2 output.
Whether or not the abnormal condition
of facility equipment during stop is
recognized can be selected.
This switch makes it possible to select
whether the forced stop signal should
be followed or neglected.
Switching of whether or not error
detection for start / stop operation from
i-Manager is done is performed.
This switch makes it possible to select
the absence or presence of later push
priority switch.
This switch makes it possible to
select whether the control output
state is maintained or not when the
transmission is abnormal.
This switch makes it possible to select
whether the system should be reset to
the state before power failure or not
when the power failure was recovered.
Whether the connected equipment
“error” is detected with contact input
“Open” or “Closed” can be selected
Connect this unit to the terminals F1, F2
of the centralized control equipment.
The power transformer connector is
connected.
Alarm
Monitor
(RED)
Contact switch
Con.
Ins.
ON
ON
ON
INPUT
Group No. Set
DS1 High
RS1 Low
Operation
Monitor
(GRN)
Set DIII-NET Adress No.
Set the switch according to the number of
facility equipment connections.
This switch makes it possible
to select whether the operation
output is interrupted or held when
an abnormality occurred in the
connected equipment.