• Control systems
• Standard protocol interfaces • BACnet Interface
Function
Major functions of air-conditioner devices
Function
Air-conditioning equipment
Remarks
VRV Inverter
series
Interface adapter
for Sky Air series
(SA Heat Pump)
HRV
Wiring adapter
for other
air-conditioners
Start/stop control and monitoring
0
0
0
0
Air-conditioner error notification
0
0
0
0
Indoor air temperature monitoring
0
0
X
X
Temperature setting and monitoring
0
0 16~32
X
X
Air-conditioning mode setting and monitoring
0
0
X
X
Air-conditioning mode switching is effective only for
indoor units for which cool/heat selection is permitted.
*1 Remote control mode setting and monitoring
0
0
X
X
Filter sign monitoring and reset
0
X
X
X
Cumulative power value monitoring
0
X
X
0
Thermostat status monitoring
0
X
X
X
Compressor operation status monitoring
0
X
X
X
Indoor fan operation status monitoring
0
X
X
X
Heater operation status monitoring
0
X
X
X
Air direction setting and monitoring
0
X
X
X
Air flow rate setting and monitoring
0
X
X
X
Forced thermostat off setting and monitoring
0 *2
X
X
X
Forced thermostat on setting and monitoring
0 *2
0 *2
X
X
Energy efficiency command (Setting temperature shift)
0
X
X
X
Notes
1 *1: Remote control mode is for acceptance or rejection of on/off operation, temperature setting and air conditioning mode setting by
remote control.
2 *2: If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3 The meaning of 0, C are as follows
0: Possible functions
C: Impossible functions