108
• Control systems
• intelligent Touch Manager • ED721208
➀
Set the top address of this equipment with the DIII-NET setting switch (DS1/RS1). Using the DIII-NET setting switch (DS1),
set the range of Adress No. that is set in this equipment. Address Nos. 1-00 to 1-15 are factory controlled before shipment.
∗
RS2
DS1
B
11
0
00
1
01
1-00 ~ 1-15
6
06
A
10
8
08
7
07
F
15
3
03
4-00 ~ 4-15
2-00 ~2-15
C
12
5
05
3-00 ~ 3-15
4
04
E
14
2
02
D
13
9
09
8
* Number of centralized addresses used
The number of centralized adresses used is determined by the top address set in this paragraph and the number of facility
equipment connected that is set in “
➄
TP1 setting (Facility equipment quantity change)” paragraph.
Example 1:
When the top address was set to “1-00” and the number of facility equipment was set to “2”, it follows that
“1-00” and “1-01” are being used.
Example 2:
When the top address was set to “3-15” and the number of facility equipment was set to “4”, it follows that
“3-15”, “4-00”, “4-01” and “4-02” are being used.
<CAUTION>
This equipment can use the addresses between “1-00” and “4-15”.
(It is impossible to use Address 5-00 and subsequent addresses, and use any address in duplication.
Example:
When the top address was set to “4-14”, the number of facility equipment cannot be set to “4”.
In this case, set it to “1” or “2”.)
➁
DS2 Setting
This switch selects whether the input is abnormal with the abnormal input contact (A1 to A4) oper or closed.
OFF (factory preset before shipment) --- Abnormal in the open condition
ON --- Abnormal in the closed condition
The relationship between each switch and abnormal input is as described below.
Input A1: DS2-1
Input A2: DS2-2
Input A3: DS2-3
Input A4: DS2-4
➂
DS4-1 Setting
This switch selects the control output status after power failure occurred in this equipment and the power was recovered.
OFF (factory preset before shipment) --- The control to power after power recovery is handled as stop output.
ON --- The control output after power recovery is handled as output before power failure.
Control range DS1 (high order)
setting (Address range)
* when a product is
discharged from the factory
This indicates the
switch knob.
<Example>
When Adress No. is
set to 1-08
Address No.
indicates the
following portion in
this case.
1-8
High
order: 1
High
order
Low
order: 8
Low
order
Set Address No. (low order) with the centralized address setting switch (RS1).
Referring to the table below, set the address number low order.
(Address Nos. are 1-00, 1-01, -- 1-15, 2-00, --- 4-15.)
In this case, it follows that this equipment uses Address Nos.
1-08 to 1-11. (4 numbers max.)
Control range DS1
Position
Address No.
RS1 Swith Setting Table
* When a product is discharged from the factory
ON
ON
ON
ON
ON