127
• Control systems
• intelligent Touch Manager • ED721208
Cautions:
1. Never use a 3 or more core of cord or cable.
2. The size of wire should be 0.75~1.25mm².
3. Never bundle the cable or cord of transmission line.
4. Be sure to keep the transmission wiring distant from power wiring as shown below to prevent electrical noise.
Capacity of power wiring
Distance between Power wiring and control wiring
Daikin air-conditioner (
★
1)
Other air-conditioners
220V or less
10A or less
50mm or more (H
★
)
300mm or more
50A or less
500mm or more
100A or less
1000mm or more
100A or more
1500mm or more
Note:
1.
★
1 .....VRV system, SkyAir series and other air-conditioner.
2.
★
2 .....VRV system or other Daikin air-conditioner produces less electrical noise, so that the distance of 50mm or more is sufficient.
For control wiring, never use the shield wire together with other sheathed vinyl cord in the same system, which may cause the
malfunction in transmission.
[Example]
50mm or more
Daikin air-conditioner
Control wiring
Power wiring for Daikin air-conditioner
High voltage wire for other equipment