75
• Control systems
• intelligent Touch Manager • ED721208
3.2.3. Connections
If you have many air conditioners, use iTM plus adaptors to connect them. It is a fact that the number of indoor groups you can control
using a single intelligent Touch Manager is limited to 64. By using iTM plus adaptors, however, you can connect additional 64 groups of
indoor units per iTM plus adaptor. Moreover, considering that the intelligent Touch Manager can be connected with a maximum of seven
iTM plus adaptors, you can control a total of 512 groups of indoor units at a maximum using a single intelligent Touch Manager.
WARNING
• Be sure to perform this procedure with the power supply turned off. Not doing so may cause
an electric shock.
• Do not clamp the cables with high-current lines such as a power cable.
Terminals location and conceptual connection diagram
Connect an iTM plus adaptor to the plus ADP IF terminals located on the rear face. Be sure to connect the positive wire the “+” terminal
and the negative wire to the “–” terminal, respectively, as these terminals have polarity.
<Terminals location and conceptual connection diagram>
A
intelligent Touch Manager (Rear face)
B
iTM plus adaptor
C
plus ADP IF (intelligent Touch Manager)
D
plus ADP IF (iTM plus adaptor)
E
iTM plus adaptor on which termination resistor must be enabled
Requirements that must be met
• Cable type: CPEV or FCPEV cable
• Core thickness: φ0.65 - 0.9 mm
• Cable length: 50 meters or less
NOTE
Each air conditioner controlled via an iTM plus adaptor is also assigned a DIII address between “1-00”
to “4-15”. From the intelligent Touch Manager, it is recognized as “2:1-00”, “3:1-02”, or the like, with the
DIII-NET port number prefixed.