Piping installation
Installer reference guide
97
08CA + EHY EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
▪
Connecting piping – Tools.
Only use appropriate tooling to handle brass, which is
a soft material. If NOT, pipes will get damaged.
▪
Connecting piping – Air, moisture, dust.
If air, moisture or dust gets into the
circuit, problems may occur. To prevent this:
-
ONLY use clean pipes.
-
Hold the pipe end downwards when removing burrs.
-
Cover the pipe end when inserting it through a wall, to prevent dust and/or
particles from entering the pipe.
-
Use a decent thread sealant to seal connections.
-
When using non-brass metallic piping, make sure to insulate both materials
from each other to prevent galvanic corrosion.
-
Because brass is a soft material, use appropriate tooling for connecting the
water circuit. Inappropriate tooling will cause damage to the pipes.
▪
Closed circuit.
Use the indoor unit ONLY in a closed water system. Using the
system in an open water system will lead to excessive corrosion.
▪
Glycol.
For safety reasons, it is NOT allowed to add any kind of glycol to the
water circuit.
▪
Piping length.
It is recommended to avoid long runs of piping between the
domestic hot water tank and the hot water end point (shower, bath,…) and to
avoid dead ends.
▪
Piping diameter.
Select the water piping diameter in relation to the required
water flow and the available external static pressure of the pump. See
234] for the external static pressure curves of the indoor
unit.
▪
Water flow.
You can find the minimum required water flow for indoor unit
operation in the following table. In all cases, this flow needs to be guaranteed.
When the flow is lower, the indoor unit will stop operation and display error 7H.
Minimum required flow rate
05 models
7 l/min
08 models
8 l/min
▪
Field supply components – Water.
Only use materials that are compatible with
water used in the system and with the materials used in the indoor unit.
▪
Field supply components – Water pressure and temperature.
Check that all
components in the field piping can withstand the water pressure and water
temperature.
▪
Water temperature – Heat pump convectors.
In case heat pump convectors are
connected, the temperature of the water in the convectors should NOT exceed
65°C. If necessary, install a thermostatic controlled valve.
▪
Water temperature – Underfloor heating loops.
In case underfloor heating
loops are connected, install a mixing station to prevent water that is too hot from
entering the underfloor heating circuit.
▪
Water temperature.
All installed piping and piping accessories (valve,
connections,…) MUST withstand the following temperatures:
INFORMATION
The following figure is an example and may NOT completely match your system
layout