Range, step
Default value
Date
Value
User settings
└─
Preset values
└─
Room temperature
7.4.1.1
R/W
[3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2
R/W
[3-07]~[3-06], step: A.3.2.4
19°C
7.4.1.3
R/W
[3-09]~[3-08], step: A.3.2.4
24°C
7.4.1.4
R/W
[3-09]~[3-08], step: A.3.2.4
26°C
└─
LWT main
7.4.2.1
[8-09]
R/W
[9-01]~[9-00], step: 1°C
45°C
7.4.2.2
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
40°C
7.4.2.3
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
7.4.2.4
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
7.4.2.5
R/W
-10~10°C, step: 1°C
0°C
7.4.2.6
R/W
-10~10°C, step: 1°C
-2°C
7.4.2.7
R/W
-10~10°C, step: 1°C
0°C
7.4.2.8
R/W
-10~10°C, step: 1°C
2°C
└─
Tank temperature
7.4.3.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
7.4.3.2
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
50°C
7.4.3.3
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
50°C
└─
Quiet level
7.4.4
R/W
0: Level 1
1: Level 2
2: Level 3
└─
Electricity price
7.4.5.1
[C-0C]
[D-0C]
R/W
0,00~990/kWh
20/kWh
7.4.5.2
[C-0D]
[D-0D]
R/W
0,00~990/kWh
20/kWh
7.4.5.3
[C-0E]
[D-0E]
R/W
0,00~990/kWh
15/kWh
└─
Fuel price
7.4.6
R/W
0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─
Set weather dependent
└─
Main
└──────────────────
Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
Low ambient temp. for LWT main zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
7.7.1.1
[1-01]
Set weather-dependent heating
High ambient temp. for LWT main zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.1.1
[1-02]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
60°C
7.7.1.1
[1-03]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~min(45,[9-00])°C, step: 1°C
35°C
└──────────────────
Set weather-dependent cooling
7.7.1.2
[1-06]
Set weather-dependent cooling
Low ambient temp. for LWT main zone cooling
WD curve.
R/W
10~25°C, step: 1°C
20°C
7.7.1.2
[1-07]
Set weather-dependent cooling
High ambient temp. for LWT main zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.1.2
[1-08]
Set weather-dependent cooling
Leaving water value for low ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
7.7.1.2
[1-09]
Set weather-dependent cooling
Leaving water value for high ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
└─
Additional
└──────────────────
Set weather-dependent heating
7.7.2.1
[0-00]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
7.7.2.1
[0-01]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~[9-06]°C, step: 1°C
60°C
7.7.2.1
[0-02]
Set weather-dependent heating
High ambient temp. for LWT add zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.2.1
[0-03]
Set weather-dependent heating
Low ambient temp. for LWT add zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└──────────────────
Set weather-dependent cooling
7.7.2.2
[0-04]
Set weather-dependent cooling
Leaving water value for high ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
7.7.2.2
[0-05]
Set weather-dependent cooling
Leaving water value for low ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
7.7.2.2
[0-06]
Set weather-dependent cooling
High ambient temp. for LWT add zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.2.2
[0-07]
Set weather-dependent cooling
Low ambient temp. for LWT add zone cooling
WD curve.
R/W
10~25°C, step: 1°C
20°C
Installer settings
└─
System layout
└─
Standard
A.2.1.1
[E-00]
R/O
0~5
3: Hybrid
A.2.1.2
[E-01]
R/O
0: 08
A.2.1.3
[E-02]
R/O
E08:
1: Type 2
EHYHBX08:
0: Type 1
A.2.1.6
[D-01]
R/W
0: No
1: Open tariff
2: Closed tariff
3: Thermostat
A.2.1.7
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
Field settings table
Installer setting at variance with
default value
Setting name
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
Comfort (heating)
Unit type
Eco (heating)
Comfort (cooling)
Eco (cooling)
Storage comfort
Storage eco
Reheat
Compressor type
Indoor software type
Unit control method
High
Medium
Low
Forced off contact