![Daikin Altherma EHYHBH05A Series Installer'S Reference Manual Download Page 101](http://html1.mh-extra.com/html/daikin/altherma-ehyhbh05a-series/altherma-ehyhbh05a-series_installers-reference-manual_4142548101.webp)
8
|
Piping installation
Installer reference guide
101
08CA + EHY EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
50
0.3
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
100
150
200
250
300
350
400
450
0
a
b
a
Pre-pressure (bar)
b
Maximum water volume (l)
Maximum leaving water temperature of 55°C for underfloor heating applications
Maximum leaving water temperature of 80°C for radiator applications
Example in case of an underfloor heating application: Maximum water volume
and expansion vessel pre-pressure in case of 55°C
Installation
height
difference
(a)
Water volume
≤280 l
>280 l
≤7 m
No pre-pressure adjustment is
required.
Do the following:
▪
Decrease the pre-pressure.
▪
Check if the water volume
does
NOT
exceed
the
maximum allowed water
volume.
>7 m
Do the following:
▪
Increase the pre-pressure.
▪
Check if the water volume
does
NOT
exceed
the
maximum allowed water
volume.
The expansion vessel of the
indoor unit is too small for the
installation. In this case, it is
recommended to install an
extra vessel outside the unit.
(a) This is the height difference (m) between the highest point of the water circuit and
the indoor unit. If the indoor unit is at the highest point of the installation, the
installation height is 0 m.
Example in case of a radiator application: Maximum water volume and
expansion vessel pre-pressure in case of 80°C
Installation
height
difference
(a)
Water volume
≤140 l
>140 l
≤7 m
No pre-pressure adjustment is
required.
Do the following:
▪
Decrease the pre-pressure.
▪
Check if the water volume
does
NOT
exceed
the
maximum allowed water
volume.
Summary of Contents for Altherma EHYHBH05A Series
Page 261: ......
Page 262: ......
Page 263: ......
Page 264: ...4P355634 1G 2022 09 Copyright 2013 Daikin Verantwortung f r Energie und Umwelt...